Yokogawa F3CX04-0N Temperature Monitoring Module The Yokogawa F3CX04-0N, also cataloged as the F3CX04 Temperature Monitoring Module, operates as a dedicated...
Read more
Available on working days between 9:00 am to 6:00 pm
Email us: sales2@industriaxplc.com
Available 24/7 for inquiries and support
Description
Yokogawa F3CX04-0N Temperature Monitoring Module
The Yokogawa F3CX04-0N, also cataloged as the F3CX04 Temperature Monitoring Module, operates as a dedicated hardware component for multi-channel temperature input processing within FA-M3 automation platforms.
HardwareSpecifications
Parameter
Specification
Model Brand
Yokogawa F3CX04-0N
Origin
Japan
Weight
200 g
Dimensions
28.9 W × 100 H × 106.1 D mm
OperatingTemp
Max allowable ambient temperature change rate: 10 degC/h
PowerConsumption
440 mA at 5 VDC
NumberOfChannels
4
InputIsolation
Isolated via photocouplers and transformers
TerminalVoltageWithstand
150 VAC tested
AlarmTypes
Input upper limit alarm, input lower limit alarm (with or without delay)
NumberOfAlarmOutputs
4 points per channel (only alarms 1 and 2 have relays)
AlarmDelayTimer
Yes
WarmUpTime
30 minutes min
MountingPosition
Horizontal only; inverted orientation not allowed
ExternalConnection
18-point terminal block with M3.5 screws
InputProcessingModes
Single-input (default), Two-input changeover
Industrial Control Features
Omron modules integrate deterministic backplane bus communication for FA-M3 systems. Firmware flash compatibility allows in-field updates without disrupting ongoing input monitoring. Channel-to-channel isolation is maintained to prevent cross-interference, supporting precise analog signal acquisition across all four inputs. Single- and two-input changeover modes allow paired or independent channel monitoring, with configurable alarm delay timers to align with system response requirements.
Frequently Asked Questions
Q: Can the F3CX04-0N be hot-swapped while the FA-M3 base module is powered? A: No. The module requires system power-down before insertion or removal to prevent signal disruption and relay misoperation.
Q: What is the maximum rate of ambient temperature change the module can tolerate? A: The module supports up to 10 degC per hour. Faster changes may affect input accuracy and alarm triggering.
Q: Are firmware updates compatible with all installed channel configurations? A: Yes, firmware flash operations preserve current input processing settings, but it is recommended to verify alarm and relay settings post-update.
Field Installation Guidelines
Mount the module horizontally on the FA-M3 base; inverted or vertical mounting is not permitted.
Ensure 18-point terminal block connections are tightened with M3.5 screws to maintain proper electrical isolation.
Route analog input wiring separately from high-current or switching circuits to minimize cross-talk.
Verify ambient temperature stability; avoid locations with rapid thermal fluctuations exceeding 10 degC per hour.
Ground module shielding appropriately to reduce electromagnetic interference and maintain signal integrity.