Yokogawa F3XD16-3F DC Input Module Configured for receiving discrete DC field signals in FA-M3 controller systems, the Yokogawa F3XD16-3F (F3XD16...
Read more
Available on working days between 9:00 am to 6:00 pm
Email us: sales2@industriaxplc.com
Available 24/7 for inquiries and support
Description
Yokogawa F3XD16-3F DC Input Module
Configured for receiving discrete DC field signals in FA-M3 controller systems, the Yokogawa F3XD16-3F (F3XD16 DC Input Module) provides direct physical/electrical execution of 24 V DC digital input acquisition from switches, sensors, and relay contacts through 16 input channels.
Hardware Specifications
Parameter
Specification
ModelBrand
Yokogawa F3XD16-3F
Origin
Japan
Weight
Approx. 175 g
Dimensions
Standard FA-M3 module form factor
OperatingTemp
Not specified in supplied data
PowerConsumption
65 mA at 5 V DC
ProductType
DC Input Module
NumberOfInputs
16
InputType
DC voltage (Sink/Source compatible)
RatedInputVoltage
24 V DC
OperatingVoltageRange
20.4 V DC to 26.4 V DC
RatedInputCurrent
4.1 mA per point at 24 V DC
InputImpedance
Approx. 5.6 kOhm
IsolationMethod
Photocoupler isolation
CommonConfiguration
16 points/common
InputResponseOFFtoON
Selectable from 62.5 us to 16 ms
InputResponseONtoOFF
Selectable from 62.5 us to 16 ms
ExternalConnection
18-point detachable terminal block with M3.5 screws
StatusIndication
Individual channel LED indicators
Channel-to-Channel Signal Isolation Characteristics
The F3XD16-3F employs photocoupler isolation between external field circuits and the internal FA-M3 logic circuitry. Optical isolation prevents direct electrical continuity between field wiring and controller electronics while reducing susceptibility to conducted electrical noise from external devices and cable runs.
The module supports both sink and source wiring configurations, allowing integration with different sensor output types without requiring separate input card variants. Input state transitions are processed using selectable filtering periods ranging from 62.5 us to 16 ms for matching field signal characteristics.
Frequently Asked Questions
Q: Does the F3XD16-3F support both sink and source input devices? A: Yes. The module is designed for DC voltage inputs and supports both sink and source wiring configurations.
Q: What isolation technology is implemented on the input channels? A: The module uses photocoupler isolation between external input circuits and the PLC internal logic circuitry.
Q: Can the input response time be adjusted for fast sensor signals? A: Yes. OFF-to-ON and ON-to-OFF response times are configurable from 62.5 us to 16 ms, allowing filtering selection according to application requirements.
FieldInstallationGuidelines
Verify field supply voltage remains within the specified 20.4 V DC to 26.4 V DC operating range before commissioning.
Route input signal cables separately from motor power conductors, contactor wiring, and variable-frequency drive output cables.
Terminate field wiring on the designated detachable terminal block and verify terminal screw tightness according to site wiring standards.
Connect cable shields according to plant grounding practices and avoid multiple shield grounding points unless required by site standards.
Confirm channel LED indications during startup to verify correct field device operation and input assignment.
De-energize the controller rack before module installation or removal unless the platform documentation explicitly permits energized replacement procedures.