Yokogawa ASI133-S00 Analog Input Module Configured for signal acquisition in CENTUM VP I/O subsystem, the Yokogawa ASI133-S00/SA3S0j8-channel (ASI133-S00 Analog Input...
Read more
Available on working days between 9:00 am to 6:00 pm
Email us: sales2@industriaxplc.com
Available 24/7 for inquiries and support
Description
Yokogawa ASI133-S00 Analog Input Module
Configured for signal acquisition in CENTUM VP I/O subsystem, the Yokogawa ASI133-S00/SA3S0j8-channel (ASI133-S00 Analog Input Module) provides direct physical/electrical execution for 4-20 mA current loop acquisition within FIO-based distributed input architecture. The module implements multi-channel analog conversion with galvanically isolated input paths and terminal-based field termination.
Suffix Breakdown & Model Matrix
No explicit structured suffix decomposition is defined in the provided reference data. The model designation is treated as a single ordering and configuration identifier:
ASI133-S00: Base module type
SA3S0j8-channel: Terminal and channel configuration reference (as provided)
Hardware Specifications
Parameter
Specification
ModelBrand
Yokogawa ASI133-S00
Origin
Japan (Yokogawa Electric Corporation)
Weight
Approx. 0.30 kg
Dimensions
13.3 cm x 14.6 cm x 3.2 cm
OperatingTemp
Not explicitly specified in source data
PowerConsumption
150 mA @ 5 VDC / 450 mA @ 24 VDC
Channels
8 channel analog input
Input Signal
4-20 mA DC current
Isolation
Channel-to-system isolated input design
Terminal Block
ATSA3S pressure clamp type
Yokogawa DCS Analog Loop Acquisition Characteristics
The ASI133-S00 operates as a field input acquisition node within Yokogawa CENTUM VP / FIO architecture, implementing 4-20 mA loop interfacing with built-in isolation per channel group. The input stage is designed for direct termination of 2-wire transmitter loops using INx.1 / INx.2 terminals with GND reference bonding. Signal conditioning supports stable current loop conversion with defined input resistance scaling under energized and de-energized states, ensuring predictable loop impedance behavior across field wiring variations.
HART-capable loop compatibility enables bidirectional digital overlay communication over the 4-20 mA carrier, allowing field device diagnostics and parameter access without external multiplexing hardware. Channel isolation structure suppresses cross-channel interference during simultaneous sampling in multi-loop configurations.
Frequently Asked Questions
Q: Can the module support hot-swap replacement under energized backplane conditions? A: Hot-swap behavior depends on CENTUM VP subsystem configuration. Electrical isolation is maintained per channel, but backplane removal must follow system-defined maintenance sequencing.
Q: Does each channel provide independent isolation? A: The module implements isolated input architecture to reduce channel interaction and protect against field-side potential differences.
Q: Is external signal conditioning required for 4-20 mA loops? A: No external conversion is required. The module directly accepts 4-20 mA inputs via terminal block interface.
Field Installation Guidelines
Use ATSA3S terminal block with correct pressure clamp termination to ensure stable loop impedance contact.
Maintain shield grounding at a single-point earth reference to avoid ground loop current injection.
Separate analog input wiring from high-voltage or switching conductors to reduce induced noise coupling.
Observe polarity on INx.1 (positive) and INx.2 (negative) for each channel loop.
Ensure loop power budget supports transmitter compliance voltage under full-scale 20 mA conditions.
Apply proper isolation testing procedures before energizing field circuits in hazardous area installations.