Yokogawa AEP9D Secondary Power Supply Bus Unit
The Yokogawa AEP9D-4, also cataloged as the AEP9D Secondary Power Supply Bus Unit, operates as a dedicated hardware component for distributing stable 24 VDC secondary power within CENTUM VP and CENTUM 3000 DCS cabinets. It receives dual-line inputs and delivers independent 9-output branches per line to connected terminal boards and sub-modules.
Hardware Specifications
Parameter
Specification
ModelBrand
AEP9D
Origin
Japan
Weight
1.8 kg nominal
Dimensions
160 mm x 130 mm x 45 mm
OperatingTemp
0 degC to 55 degC
PowerConsumption
Max input current: 20 A total; 10 A per port
InputPowerSupplyVoltage
24 VDC
WithstandingVoltage
500 V AC, 1 min
OutputPorts
9 per line, 3-pin MATE-N-LOK
StandardsConformance
CSA, CE Marking
InputTerminals
Line A/B: +24P, –24N; FG functional ground
OutputPinAssignments
Pin1: FG, Pin2: –24N, Pin3: +24P
Channel-to-Channel Isolation
The AEP9D ensures electrical isolation between Line A and Line B output channels, preventing cross-channel interference. Each output port maintains separation from adjacent ports to minimize ground loop currents and protect downstream control modules. This isolation supports stable 4-20 mA HART loop signaling and prevents propagation of transient voltage spikes across connected devices.
Frequently Asked Questions
Q: Does the AEP9D support hot-swapping of input lines? A: Input lines can be maintained individually; however, hot-swap procedures require sequential disconnection to avoid output voltage collapse on dependent loads.
Q: What is the switching behavior during line redundancy activation? A: Switching between Line A and Line B occurs automatically without mechanical relays, ensuring minimal transient impact within 1-2 ms for downstream circuits.
Q: Can the output ports handle extended cable runs without voltage drop? A: The outputs are designed for distribution within the standard cabinet environment. For runs exceeding 5 m, voltage drop must be evaluated according to cable AWG and current rating.
Field Installation Guidelines
Mount the AEP9D on a grounded DIN rail or bracket ensuring functional ground connection to cabinet chassis.
Route Line A and Line B separately, avoiding parallel routing to high-power AC conductors.
Connect each output branch to intended terminal boards using 3-pin MATE-N-LOK connectors, maintaining polarity (+24P, –24N, FG).
Verify total input current does not exceed 20 A; balance loads per line to prevent thermal overload.
Ensure environmental airflow allows operation within 0 degC to 55 degC; avoid obstructing cooling paths.