    Description

    Yokogawa ADV551-P50/D5A00 Digital Output Modules

    Configured for 32-channel discrete signal execution in CENTUM-compatible DCS architectures, the Yokogawa ADV551-P50/D5A00 (ADV551 Digital Output Modules) provides direct current sink output handling for field-side status and pulse transmission circuits. The module integrates pulse width output capability together with a KS Cable Interface Adapter for 32-channel digital interfacing.

    Suffix Breakdown & Model Matrix

    Code Segment Description
    ADV551 Digital Output Module
    P With pulse width output function/time-proportional output function
    5 Without status display; without explosion protection
    0 Basic type
    /D5A00 With KS Cable Interface Adapter for 32-channel Digital (ATD5A-00)

    Hardware Specifications

    Parameter Specification
    Model ADV551-P50/D5A00
    Brand Yokogawa
    Product Type Digital Output Modules
    Number of Channels 32
    Rated Input Voltage 24 V DC
    Load Voltage 24 V DC, 50 mA
    Output Format Current sink
    External Power Supply Range 20.4 to 26.4 V DC
    Output Response Time 3 ms max (status output), 10 ms max (mixed status/pulse output)
    Pulse Width Range 8 ms to 7200 s
    Pulse Width Resolution 8 ms
    Withstanding Voltage 2 kV AC for 1 minute between output signal and system
    Common Isolation Voltage 500 V AC for 1 minute between commons
    Isolation Structure Common minus (-) side every 16 channels
    Option Adapter ATD5A-00 KS Cable Interface Adapter
    Weight 0.2 kg
    Origin Japan

    Channel Isolation and DCS Signal Integrity

    The ADV551-P50/D5A00 module implements grouped common isolation architecture with separation applied every 16 channels on the common minus side. This arrangement reduces inter-channel interference during simultaneous status and pulse output operation within distributed control system signal paths.

    The current sink output structure is intended for 24 V DC field-side switching circuits where external supply regulation remains within the specified 20.4 to 26.4 V DC operating window. Pulse width output handling supports both short-duration command pulses and extended time-proportional output cycles up to 7200 s.

    Dielectric isolation ratings include 2 kV AC withstand capability between output signals and system circuitry, together with 500 V AC isolation between grouped commons for one minute test duration.

    Frequently Asked Questions

    Q: Does the ADV551-P50/D5A00 support pulse-based output operation?
    A: Yes. The module includes pulse width output and time-proportional output functions with selectable pulse durations from 8 ms to 7200 s.

    Q: What output topology is used by the module?
    A: The module uses a current sink output format intended for 24 V DC discrete field output circuits.

    Q: Are all 32 channels isolated individually?
    A: No. The common minus side is grouped in 16-channel sections with isolation applied between commons according to the specified 500 V AC withstand rating.

    Field Installation Guidelines

    • Verify external field supply voltage remains within the specified 20.4 to 26.4 V DC range before energizing output circuits.

    • Separate pulse output wiring from high-current motor or relay cabling to reduce inductive noise coupling into digital signal paths.

    • Maintain shield grounding at a single designated control cabinet grounding point to prevent ground loop circulation.

    • Confirm KS Cable Interface Adapter alignment and connector seating before applying field power to the module assembly.

    • Do not route low-level signal cables in parallel with AC mains conductors inside shared cable trays without metallic segregation.

    Specifications

    • Brand: Yokogawa

    Advantages

    • High reliability in industrial environments
    • Supports continuous operation
    • Compatible with major PLC/DCS systems

    Customer Reviews

    Be the first to write a review
    0%
    (0)
    0%
    (0)
    0%
    (0)
    0%
    (0)
    0%
    (0)
    Send us a message!

    Do you need a large stock? Contact us.

    Collections you may also like

    Recently viewed products

      Login

      Forgot your password?

      Don't have an account yet?
      Create account