Available on working days between 9:00 am to 6:00 pm
Email us: sales2@industriaxplc.com
Available 24/7 for inquiries and support
Description
Yokogawa AAM10 Current/Voltage Input Module
Configured for acquisition of 4-20 mA DC and 1-5 V DC process signals in Yokogawa CENTUM CS/VP I/O architectures, the Yokogawa AAM10 (AAM10 Current/Voltage Input Module) provides direct physical and electrical signal conversion into DCS digital input data streams.
Suffix Breakdown & Model Matrix
The AAM10 is defined as a single fixed hardware model. No factory-published suffix segmentation or option code matrix is specified in the provided documentation.
Hardware Specifications
Parameter
Specification
ModelBrand
Yokogawa AAM10
PowerConsumption
250 mA or less at 5.0 VDC
Input Signal
4-20 mA DC, 1-5 V DC
Input Resistance (Voltage)
1 MOhm (100 kOhm at power-down)
Input Resistance (Current)
250 Ohm
Allowable Input Range
-10 VDC to 30 VDC, 40 mA DC max
Transmitter Power Supply
25.0 to 25.5 VDC, 60 mA current limit
Data Update Period
50 ms
Isolation
Input-to-system galvanic isolation
Withstanding Voltage
1500 VAC for 1 minute
Yokogawa DCS Channel-to-Channel Signal Conditioning Behavior
The Yokogawa AAM10 implements DCS-grade analog front-end conditioning with software-selectable voltage/current acquisition paths. In current loop mode, the 250 Ohm shunt conversion path enables direct 4-20 mA DC signal translation into measurable voltage levels for A/D conversion. The integrated transmitter power supply (25.0 to 25.5 VDC) supports 2-wire loop-powered devices without external excitation hardware.
Channel isolation design separates field input circuitry from internal CENTUM backplane logic, reducing ground loop propagation through the I/O nest structure. The module maintains stable measurement behavior under ambient temperature variation, with defined drift limits in both voltage and current acquisition channels.
Frequently Asked Questions
Q: Can the AAM10 module directly power 2-wire transmitters? A: Yes. It provides an integrated 25.0 to 25.5 VDC loop supply with 60 mA current limitation for 2-wire field instruments.
Q: What is the analog conversion cycle of the module? A: The data update period is fixed at 50 ms, representing the module-level sampling refresh interval.
Q: Is input isolation implemented per channel or per module? A: Isolation is implemented between field inputs and the internal DCS system domain at module level.
Field Installation Guidelines
Install the module into the designated I/O Module Nest or Node Interface Unit only.
Use M4 screw terminals for field wiring termination with controlled torque per site standard practice.
Maintain shield continuity and terminate cable shields at a single ground point to reduce loop-induced noise.
Verify correct configuration of voltage vs current input mode before energizing field loops.
Ensure loop-powered transmitters do not exceed the 60 mA supply limit per channel group.