ABB TB807 Modulebus Terminator The ABB 3BSE008538R1, also cataloged as the TB807 Modulebus Terminator, operates as a passive termination unit...
Read more
Available on working days between 9:00 am to 6:00 pm
Email us: sales2@industriaxplc.com
Available 24/7 for inquiries and support
Description
ABB TB807 Modulebus Terminator
The ABB 3BSE008538R1, also cataloged as the TB807 Modulebus Terminator, operates as a passive termination unit for completing Modulebus communication lines within ABB S800 I/O system configurations.
Hardware Specifications
Parameter
Specification
Model
TB807 3BSE008538R1
Brand
ABB
Product Type
Modulebus Termination Unit
Origin
Sweden
Weight
10 g
Dimensions
Width: 17 mm; Depth: 13 mm; Height: 19 mm
Operating Temp
0 to +55 deg C
Storage Temperature
-25 to +70 deg C
Power Consumption
Passive unit, no external power consumption
Mechanical Platform
S800
Protection Class
IP20 according to IEC 60529
Pollution Degree
Degree 2 according to IEC 60664-1
Electrical Safety
IEC 61131-2, UL 61010-1, UL 61010-2-201
EMC Compliance
EN 61000-6-4 and EN 61000-6-2
Corrosion Protection
ISA-S71.04: G3
RoHS Compliance
EU RoHS, UAE RoHS, CN RoHS
WEEE Compliance
Directive 2012/19/EU
Hazardous Location Certification
C1 Div 2 cULus, C1 Zone 2 cULus, ATEX Zone 2
Marine Certification
ABS, BV, DNV, LR
Modulebus Termination Function
The ABB TB807 provides physical termination for the S800 Modulebus network. The unit completes the communication bus structure by applying the required termination impedance at the end of the Modulebus segment. Therefore, it prevents signal reflections and maintains correct bus electrical characteristics.
The TB807 uses a passive design without active electronics or external power input. Additionally, its compact S800 mechanical format supports installation within ABB I/O assemblies where space requirements apply.
Frequently Asked Questions
Q: What is the primary function of the ABB TB807? A: The TB807 functions as a passive Modulebus termination unit. It terminates the end of an S800 Modulebus segment and maintains proper bus signal conditions.
Q: Does the TB807 require a power supply connection? A: No. The TB807 is a passive component and does not require external power or firmware configuration.
Q: Which ABB system platform uses the TB807? A: The TB807 belongs to the ABB S800 mechanical platform and is designed for Modulebus termination applications.
Field Installation Guidelines
Install the TB807 at the designated end position of the Modulebus communication segment according to ABB system configuration requirements.
Verify that the termination unit is installed securely within the S800 hardware assembly.
Maintain proper cable routing and avoid parallel installation with high-current power conductors to reduce electromagnetic interference.
Follow ABB grounding and shielding practices for Modulebus cable installations.
Confirm that environmental conditions remain within the specified operating temperature, humidity, and protection class limits.
Inspect mechanical connections during commissioning to ensure correct physical placement and bus continuity.