Description
The General Electric IC660BBS103 is a Genius Block I/O module designed for industrial control applications. This discrete output block provides eight (8) output circuits, supporting a nominal voltage of 115 VAC or 125 VDC. It is engineered for robust performance in demanding environments, featuring comprehensive diagnostic capabilities to monitor system health and operational status.
Features
- Eight (8) discrete output circuits.
- Supports 115 VAC and 125 VDC nominal voltage ranges.
- Integrated diagnostics for output monitoring, including short circuit, overload, no load, overtemperature, and loss of I/O power detection.
- Internal electronic short circuit protection with defined trip times.
- Designed for integration within the Genius I/O system architecture.
Technical Specifications
| Model |
IC660BBS103 |
| Module Type |
Discrete Output Block |
| Number of Circuits |
8 |
| Nominal Voltage |
115 VAC / 125 VDC |
| Output Current (AC) |
2 A RMS |
| Output Current (DC) |
2 A Resistive / 1 A Inductive |
| Peak Block Output |
15 A |
| Operating Temperature |
0 to 60 degC |
| Relative Humidity |
5 to 95% (non-condensing) |
Installation Guidelines
- Ensure the control system power is disconnected before installing or removing the block.
- Mount the module in a location that allows for adequate ventilation to maintain operating temperatures within the specified 0 to 60 degC range.
- Verify that all wiring connections are secure and comply with local electrical codes.
- Use shielded cables where necessary to minimize electromagnetic interference (EMI) in high-noise industrial environments.
- Handle the module using proper ESD (Electrostatic Discharge) precautions to prevent damage to internal circuitry.
FAQ
What type of diagnostics does the IC660BBS103 support?
The module supports output diagnostics including short circuit, overload, no load, overtemperature, and loss of I/O power.
What is the maximum output current for this block?
The peak block output is 15 Amps, with individual circuit ratings of 2 A RMS for AC and 2 A resistive (1 A inductive) for DC.