    Description

    Honeywell MC-TDIA12 51304439-175 Isolated Digital Input Board

    The Honeywell MC-TDIA12 51304439-175, also cataloged as the MC-TDIA12 Isolated Digital Input Board, operates as a dedicated hardware component for AC digital signal acquisition within Honeywell control system I/O architectures.

    Hardware Specifications

    Parameter Specification
    Model MC-TDIA12 51304439-175
    Brand Honeywell
    Product Type Isolated Digital Input Board
    Spare Model 51304439-175
    Origin USA
    Weight 1.14 kg
    Dimensions 46.2 x 12 x 5 cm
    Input Channels 32
    Digital Input Voltage 90-132 VAC rms
    Frequency Range 47-63 Hz
    Galvanic Isolation 1500 VAC rms or +/-1500 VDC
    Sense Current 3.5 mA minimum
    Absolute Delay Across Input Filter and Isolation 25 ms maximum
    Accumulated Input Frequency Not applicable
    Tariff Code 8537101190
    Shipment Location Xiamen, China

    Channel-to-Channel Isolation and DCS Signal Processing

    The Honeywell MC-TDIA12 51304439-175 uses isolated digital input channels to acquire field AC status signals and transfer discrete states into the control system. The board supports 32 input channels and accepts 90-132 VAC rms field signals.

    Furthermore, the module applies galvanic isolation between field circuits and internal electronics. The isolation rating reaches 1500 VAC rms or +/-1500 VDC, which separates external wiring conditions from the control hardware signal path.

    For Honeywell process control systems, channel-to-channel isolation supports discrete field device monitoring where electrical separation is required. The input circuit design manages switching signals with a maximum delay of 25 ms across the input filter and isolation stages.

    Frequently Asked Questions

    Q: What type of field signals does the Honeywell MC-TDIA12 51304439-175 accept?
    A: The MC-TDIA12 accepts 90-132 VAC rms digital input signals with a frequency range of 47-63 Hz.

    Q: Does the MC-TDIA12 provide electrical isolation between field inputs and internal circuits?
    A: Yes. The board provides galvanic isolation rated at 1500 VAC rms or +/-1500 VDC.

    Q: How many digital input channels are available on this board?
    A: The MC-TDIA12 provides 32 isolated digital input channels for discrete signal acquisition.

    Field Installation Guidelines

    • Install the MC-TDIA12 51304439-175 according to the Honeywell system hardware configuration and approved cabinet wiring practices.
    • Verify that field wiring voltage levels match the specified 90-132 VAC rms digital input range before connection.
    • Separate AC digital input wiring from low-level analog signal cables to reduce electrical interference.
    • Connect cable shields according to the control cabinet grounding design and site electrical standards.
    • Check terminal connections for correct polarity and secure mechanical fastening before system startup.
    • Confirm isolation requirements when connecting field devices located in electrically noisy environments.
    • Avoid routing signal cables near high-current power conductors unless proper separation or shielding methods are applied.

    Specifications

    • Brand: Honeywell

    Advantages

    • High reliability in industrial environments
    • Supports continuous operation
    • Compatible with major PLC/DCS systems

    Customer Reviews

    Be the first to write a review
    0%
    (0)
    0%
    (0)
    0%
    (0)
    0%
    (0)
    0%
    (0)
    Send us a message!

    Do you need a large stock? Contact us.

    Collections you may also like

    Recently viewed products

      Login

      Forgot your password?

      Don't have an account yet?
      Create account