Honeywell FC-PSUNI2424 Power Supply Unit Configured for 24 VDC power conversion and overvoltage protection execution in industrial control power networks,...
Read more
Available on working days between 9:00 am to 6:00 pm
Email us: sales2@industriaxplc.com
Available 24/7 for inquiries and support
Description
Honeywell FC-PSUNI2424 Power Supply Unit
Configured for 24 VDC power conversion and overvoltage protection execution in industrial control power networks, the Phoenix Contact FC-PSUNI2424 (PSUNI2424 Power Supply Unit) provides direct physical and electrical power regulation.
Hardware Specifications
Parameter
Specification
Model
FC-PSUNI2424
Brand
Honeywell
Origin
Not specified
Weight
2.9 kg
Dimensions
370 x 159 x 67.3 mm (W x H x D)
Operating Temp
-40 deg C to 70 deg C
Power Consumption
600 W output power; input power 712 W at 115 VAC, 691 W typical at 230 VAC
Input Voltage
100-120 VAC / 220-240 VAC nominal; operational range 85-265 VAC
Input Frequency Range
45-66 Hz
Input Current
6.2 A at 115 VAC; 3.1 A at 230 VAC at rated DC output load
Output Voltage
25.7 V no load; 25.1 V with 24 A static load
Output Power
600 W
Power Efficiency
80% at 100 VAC and 6 A; 84.5% at 100 VAC and 12-24 A; 82% at 230 VAC and 6 A; 87% at 230 VAC and 12-24 A
Power Factor
>0.99 at 100 VAC and 6-24 A; >0.88 at 230 VAC and 6 A; 0.98 at 230 VAC and 24 A
Inrush Current
<60 A; supports 10 A Type C circuit breaker
Internal Fuse
10 A fuse for each AC leg line
External Protection
10 A Class CC fuse or 10-13 A Type C MCB according to EN60898-1
EMC Standards
EN61131-2, EN50130-4, EN61000-6-7
Approvals
CE; cUL 60950
Safety Certification
DC output SELV certified; OVP SIL3 certified according to IEC 61508
Storage Temperature
-40 deg C to 85 deg C; keep below 40 deg C for long-term storage
Humidity
5% to 95% RH non-condensing; derating above 40 deg C
Pollution Degree
PD2 maximum according to IEC60664-1
Altitude
0-2000 m above sea level
Installation Category
Industrial installations only; OVC II up to 2000 m
DIN-Rail Power Conversion and Protection Characteristics
The FC-PSUNI2424 integrates regulated DC power conversion with output voltage supervision functions. The unit maintains a 24 VDC supply output while the integrated overvoltage protection circuit limits DC output voltage below 31 V according to IEC 61508 SIL3 requirements.
Additionally, the power supply includes input EMI filtering with a 2 uF capacitor network between input lines. The design supports industrial AC supply variations from 85 VAC to 265 VAC and maintains controlled inrush current characteristics for circuit breaker coordination.
The PSUNI2424 uses DIN-rail industrial installation principles and provides surge voltage protection limits suitable for control cabinet power distribution. Therefore, installers must maintain proper grounding, protective earth connection, and separation between AC input wiring and low-voltage DC output circuits.
Frequently Asked Questions
Q: Does the FC-PSUNI2424 provide SELV classified DC output? A: Yes. The DC output is SELV certified, and the integrated overvoltage protection maintains output voltage below 31 V according to IEC 61508 SIL3 requirements.
Q: What external circuit protection is specified for the FC-PSUNI2424? A: The input circuit supports a 10 A Class CC fuse or a 10-13 A Type C MCB according to EN60898-1.
Q: Can the power supply operate in high humidity environments? A: Yes. The unit supports 5% to 95% RH non-condensing humidity, with output derating required above 40 deg C.
Field Installation Guidelines
Install the FC-PSUNI2424 inside an industrial control cabinet with adequate ventilation clearance around the enclosure. Connect the protective earth conductor according to applicable electrical installation standards before applying AC input power.
Route AC input conductors separately from 24 VDC output wiring and sensitive signal cables to reduce electromagnetic interference. Maintain correct polarity on the DC output terminals and verify the output voltage before connecting downstream automation equipment.
Use the specified external fuse or circuit breaker protection device to coordinate input protection. Check cabinet temperature conditions because output capability decreases when operating humidity and ambient temperature exceed specified limits.