Honeywell 900A16-0301 High-Level Analog Input Module The Honeywell 900A16-0301, also cataloged as the 900A16-0301 High-Level Analog Input Module, operates as...
Read more
Available on working days between 9:00 am to 6:00 pm
Email us: sales2@industriaxplc.com
Available 24/7 for inquiries and support
Description
Honeywell 900A16-0301 High-Level Analog Input Module
The Honeywell 900A16-0301, also cataloged as the 900A16-0301 High-Level Analog Input Module, operates as a dedicated hardware component for analog signal acquisition within the Honeywell ControlEdge HC900 controller system. It receives voltage and current field signals through 16 isolated input channels and performs local analog-to-digital conversion for controller execution.
Hardware Specifications
Parameter
Specification
Model
900A16-0301
Brand
Honeywell
Origin
USA
Dimensions
111.1 mm x 94.0 mm x 66.0 mm
Operating Temp
0 deg C to 60 deg C
Power Consumption
+5 V rail: 75 mA max; +24 V rail: 50 mA max
Product Type
16-Point High-Level Analog Input Module
Product Family
Honeywell ControlEdge HC900
Input Channels
16 isolated analog input channels
Input Configuration
User-configurable voltage or current input per channel
Voltage Input Ranges
0 to 1 V, 0 to 2 V, 0 to 5 V, 0 to 10 V
Current Input Ranges
0 to 20 mA, 4 to 20 mA
Current Input Conversion
Integrated 250 ohm shunt resistor selectable by DIP switch
A/D Converter Resolution
15 bits
Update Rate
100 ms
Accuracy
+/-0.1% of reading typical
Channel Isolation
400 VDC point-to-point galvanic isolation
Logic and Chassis Isolation
1 kVDC
Terminal Interface
36-terminal removable Euro-style or barrier-style terminal block
Operating Humidity
10% to 90% RH non-condensing
Storage Temperature
-40 deg C to 70 deg C
Environmental Protection
G3 conformal coating standard except power supplies
Process Control Analog Signal Interface
The Honeywell 900A16-0301 supports direct connection of industrial analog transmitters and field instruments through configurable voltage and current inputs. Each channel operates with independent isolation to prevent signal interference between measurement points.
The module architecture uses local microcontroller processing to synchronize analog conversion with ControlEdge HC900 CPU execution. Therefore, the system reduces data transfer latency between the I/O module and controller processing cycle.
For current loop applications, the integrated 250 ohm shunt resistor converts 4-20 mA and 0-20 mA signals into voltage inputs for analog measurement. Additionally, the isolated channel design supports separated field wiring arrangements and reduces common signal coupling.
Frequently Asked Questions
Q: Does the Honeywell 900A16-0301 support 4-20 mA field transmitter signals? A: Yes. The module supports 4-20 mA and 0-20 mA current inputs with selectable 250 ohm shunt resistors for current signal conversion.
Q: How does the module provide isolation between analog input channels? A: The module provides 400 VDC galvanic isolation between individual input channels and 1 kVDC isolation between field circuits and logic/chassis circuits.
Q: Can the input range be configured independently for each channel? A: Yes. Each input point can be configured separately for supported voltage or current measurement ranges according to the application requirements.
Field Installation Guidelines
Install the 900A16-0301 module in the designated ControlEdge HC900 I/O rack slot according to the controller hardware configuration.
Use the specified removable terminal block interface for field wiring connections.
Separate analog signal cables from high-voltage power wiring and switching circuits to reduce electrical noise coupling.
Connect cable shields according to plant grounding standards and avoid multiple-point shield grounding on sensitive analog loops.
Verify channel configuration before connecting field transmitters, including voltage range, current range, and shunt resistor selection.
Confirm field device polarity and signal reference connections before applying power to the module.
Check controller diagnostics after installation to verify channel status and analog input scaling.