Description
Product Description
The Honeywell 2106B2312 is a high-temperature catalytic bead sensor from the Sensepoint HT series, designed to detect combustible gases in demanding industrial environments. Engineered for continuous operation up to +150 °C, it is ideal for high-temperature applications such as turbine enclosures, drying ovens, and solvent-based processing equipment. Its robust 316 stainless steel housing and poison-resistant design ensure reliable performance in harsh, contaminated atmospheres. The sensor provides fast, accurate readings over a wide detection range while maintaining compliance with ATEX and IECEx safety standards.
Technical Specifications
| Specification |
Details |
| Sensor Type |
Catalytic bead combustible gas sensor |
| Series |
Sensepoint HT (High Temperature) |
| Detection Range |
0–100% LEL (Lower Explosive Limit) |
| Alarm Trip Points |
From 5% LEL |
| Operating Temperature |
-55 °C to +150 °C (-67 °F to +302 °F) |
| Operating Humidity |
20–90% RH continuous; 10–99% RH intermittent (non-condensing) |
| Operating Pressure |
90–110 kPa |
| Power Supply |
2.9–3.5 V bridge at 200 mA (~700 mW) |
| Signal Output |
mV bridge output |
| Response Time |
Fast response, resistant to poisoning |
| Construction |
316 stainless steel body |
| Thread Type |
3/4" NPT |
| Weight |
323 g |
Key Features & Advantages
-
Certified for continuous high-temperature operation up to +150 °C
-
Durable stainless steel housing for harsh environments
-
Poison-resistant catalytic bead design ensures long-term accuracy
-
Flexible detection range from 0–20% to 0–100% LEL
-
ATEX and IECEx certified for use in explosive atmospheres
-
Extended operational life reduces maintenance and replacement frequency
Applications
The Honeywell 2106B2312 is recommended for:
-
Turbine enclosures and power generation equipment
-
Drying ovens and high-temperature industrial processes
-
Solvent-based printing, coating, and chemical processing machines
-
Safety-critical combustible gas detection in hazardous areas
FAQ
Q: Can this sensor detect toxic gases?
A: No, the 2106B2312 is designed specifically for combustible gases. For toxic gas detection, select a dedicated toxic gas sensor.
Q: What is the maximum operating temperature?
A: The sensor operates reliably up to +150 °C (+302 °F).
Q: How long is the typical sensor life?
A: The catalytic bead design ensures over 5 years of reliable operation under normal conditions.
Q: Which controllers are compatible?
A: Requires Honeywell gas detection controllers capable of processing mV bridge signals from Sensepoint HT sensors.