GE Multilin URGHH UR-GHH Universal Relay Hardware Module Configured for digital protection and control execution in GE Multilin Universal Relay...
Read more
Available on working days between 9:00 am to 6:00 pm
Email us: sales2@industriaxplc.com
Available 24/7 for inquiries and support
Description
GE Multilin URGHH UR-GHH Universal Relay Hardware Module
Configured for digital protection and control execution in GE Multilin Universal Relay (UR) Series platforms, the GE Multilin URGHH (URGHH Hardware Module) provides direct physical/electrical execution within modular protection relay architectures. The module supports configurable CT/VT acquisition, digital I/O processing, communication interfaces, and programmable protection logic functions.
Hardware Specifications
Parameter
Specification
Model
URGHH
Brand
GE Multilin
Weight
2 lb
Dimensions
6.5 in L x 6.5 in W x 1.75 in H
Operating Temp
-40 deg C to +60 deg C (-40 deg F to +140 deg F)
Power Consumption
Depends on configured UR hardware assembly
Device Type
Microprocessor-based Digital Protection & Control Relay Module
Platform
GE Multilin Universal Relay (UR) Series
System Architecture
Modular chassis with field-replaceable CPU, power supply, I/O, and CT/VT modules
Control Logic Engine
FlexLogic programmable logic engine
Power Supply Options
110-250 VDC / 110-230 VAC or 24-48 VDC hardware options
CT Inputs
1 A / 5 A secondary rated current
VT Inputs
60-300 VAC secondary rated voltage
Digital Inputs
Optically isolated digital inputs
Relay Outputs
Form-A / Form-C latching and fast-acting relay outputs
Communication Protocols
IEC 61850, Modbus RTU/TCP, DNP3.0, IEEE 1588 PTP
Ethernet Interfaces
Redundant 10/100Base-T RJ45 or 100Base-FX fiber ports
Network Functions
PRP and HSR support
Front Interface
Graphical display, programmable LEDs, local control keys
Enclosure Protection
IP54 front panel, IP20 rear terminals
Software Interface
EnerVista UR
Certifications
CE, UL/cUL, IEEE C37.90, IEC 60255 series
GE Multilin UR Series Communication and Control Architecture
The URGHH operates as part of the GE Multilin Universal Relay modular hardware environment. The architecture uses replaceable functional modules for processing protection algorithms, measurement acquisition, communication handling, and local control execution.
The platform supports deterministic network communication through IEC 61850, Modbus, DNP3.0, and IEEE 1588 Precision Time Protocol. Ethernet options include redundant copper and fiber interfaces with PRP/HSR network redundancy support.
Firmware flash compatibility is managed through the EnerVista UR software environment, allowing supported configuration files and firmware packages to be applied according to the installed UR hardware configuration.
Frequently Asked Questions
Q: Can the URGHH module operate as a standalone protection relay? A: No. The URGHH is a hardware configuration/module variant within the GE Multilin Universal Relay platform and requires integration with the corresponding UR chassis assembly and configured system modules.
Q: What type of field wiring interfaces are supported? A: The Universal Relay hardware architecture supports CT/VT secondary inputs, optically isolated digital inputs, relay output contacts, and communication interfaces through the installed module configuration.
Q: Does the module support redundant communication networks? A: The UR platform supports redundant Ethernet configurations including PRP and HSR functions when compatible communication hardware is installed.
Field Installation Guidelines
Install the module only within the designated GE Multilin Universal Relay chassis position defined by the hardware configuration.
Verify CT and VT secondary wiring polarity before energizing protection circuits.
Separate communication wiring from high-voltage switching conductors to reduce electrical interference.
Use shielded communication cables where required by the installation environment and terminate cable shields according to site grounding practices.
Confirm rear terminal connections are mechanically secured before applying auxiliary power.
Verify installed firmware compatibility with the configured UR hardware modules before commissioning.
Maintain required enclosure protection levels after panel installation and wiring completion.