Over 100,000 PLC, DCS, Drive, TSI & MRO Parts In Stock Learn more

GE Multilin 750-P5-G5-S1-HI-A20-R-E Feeder Protection Relay

GE Multilin 750-P5-G5-S1-HI-A20-R-E Feeder Protection Relay

Product form

GE Multilin 750-P5-G5-S1-HI-A20-R-E Feeder Protection Relay The GE Multilin 750-P5-G5-S1-HI-A20-R-E, also cataloged as the 750 Feeder Protection Relay, operates as a dedicated hardware... Read more

SKU: 750-P5-G5-S1-HI-A20-R-E
Country of origin: USA

      100% Original and Authentic

    Do you need a large stock? Contact us.

      100% Brand New,Ready to ship

    Do you need a large stock? Contact us.

      Support Refund,7X24h Service

    Support Refund,7X24h Service , Contact us.

      Call us: +86 153 9592 3051

    Available on working days between 9:00 am to 6:00 pm

      Email us: sales2@industriaxplc.com

    Available 24/7 for inquiries and support

    Description

    GE Multilin 750-P5-G5-S1-HI-A20-R-E Feeder Protection Relay

    The GE Multilin 750-P5-G5-S1-HI-A20-R-E, also cataloged as the 750 Feeder Protection Relay, operates as a dedicated hardware component for feeder current monitoring, protection execution, and electrical network control within GE Multilin 750/760 series platforms.

    Hardware Specifications

    Parameter Specification
    Model GE Multilin 750-P5-G5-S1-HI-A20-R-E
    Brand GE Multilin
    Origin United States
    Operating Temp -40 deg C to +60 deg C
    Power Consumption 15 to 25 W nominal, 45 W maximum
    Product Type Feeder Protection Relay
    Series GE Multilin 750/760 Series
    Mounting Type Drawout case, flush mounting
    Power Supply 90 to 300 V AC, 125 to 250 V DC
    Phase CT Input 5 A nominal
    Ground CT Input 5 A nominal
    Sensitive Ground CT Input 1 A nominal
    Frequency Tracking 16 Hz to 65 Hz automatic tracking
    Communication Ports RS232, dual RS485, optional Ethernet
    Communication Protocols Modbus RTU, DNP 3.0
    Digital Inputs 14 optically isolated dry contact inputs
    Output Contacts 8 Form-A / Form-C relay outputs
    Analog Inputs 4 isolated analog inputs, selectable 0-1 mA / 4-20 mA
    Analog Outputs 8 configurable analog outputs, selectable 0-1 mA / 0-20 mA / 4-20 mA
    Protection Functions 50P/51P, 50G/51G, 50N/51N, 50SG/51SG, 27/59, 81O/81U, 46, 49, 79, 25
    Front Protection Rating IP54 front panel
    Environmental Coating Conformal coating option for harsh environments

    Industrial Control Communication and Firmware Compatibility

    The GE Multilin 750 series relay uses embedded microprocessor control architecture with configurable protection logic, metering functions, and communication interfaces. The unit supports RS232 and RS485 Modbus RTU communication channels, with optional Ethernet expansion capability. Firmware compatibility is managed through GE Multilin configuration tools and supported hardware revisions.

    The relay supports deterministic data exchange between protection functions, metering channels, and supervisory systems. Configuration parameters include protection pickup levels, timing curves, input/output assignments, and communication settings.

    Frequently Asked Questions (FAQ)

    Q: Does the GE Multilin 750-P5-G5-S1-HI-A20-R-E support hot-swappable replacement?
    A: The relay uses a drawout case design. Removal or insertion should follow the applicable electrical isolation procedure, as protection hardware replacement is not specified as a powered hot-swap operation.

    Q: What CT inputs are supported by this model configuration?
    A: The P5 option provides 5 A phase CT inputs, the G5 option provides 5 A ground CT inputs, and the S1 option provides 1 A sensitive ground CT input.

    Q: What communication interfaces are available for integration with control systems?
    A: The relay provides front RS232 and rear dual RS485 ports supporting Modbus RTU and DNP 3.0 protocols. Optional Ethernet communication is available through an expansion module.

    Field Installation Guidelines

    Install the relay in a compatible drawout panel assembly with correct mechanical alignment of the case and terminal connections.

    Current transformer wiring should maintain proper polarity and phase identification. CT secondary circuits must remain isolated from unrelated signal wiring and should follow site grounding practices.

    Communication cables should be routed separately from high-current power conductors. Shielded communication wiring should use appropriate termination and grounding methods according to the installation environment.

    The conformal coating option should be considered where the relay is exposed to humidity, salt contamination, or airborne corrosive materials. Verify power supply voltage range before energizing the control supply terminals.

    Specifications

    • Brand: General Electric

    Advantages

    • High reliability in industrial environments
    • Supports continuous operation
    • Compatible with major PLC/DCS systems