GE IS230STCIH6A Simplex Thermocouple Input Terminal Board The GE IS230STCIH6A, also cataloged as the IS230STCIH6A Simplex Thermocouple Input Terminal Board, operates as a...
Read more
Available on working days between 9:00 am to 6:00 pm
Email us: sales2@industriaxplc.com
Available 24/7 for inquiries and support
Description
GE IS230STCIH6A Simplex Thermocouple Input Terminal Board
The GE IS230STCIH6A, also cataloged as the IS230STCIH6A Simplex Thermocouple Input Terminal Board, operates as a dedicated hardware component for thermocouple temperature signal acquisition within GE Mark VIe Speedtronic control systems. The board provides conditioned analog temperature inputs from field sensors to turbine controller processing channels.
Hardware Specifications
Parameter
Specification
Model
IS230STCIH6A
Brand
GE
Origin
United States
Weight
0.5 kg
Operating Temp
-30 deg C to +65 deg C
Power Consumption
Not specified
Series
Mark VIe Speedtronic Control System
Product Type
Simplex Thermocouple Input Terminal Boards
Input Channels
12 thermocouple input channels
Supported Thermocouple Types
Type E, J, K, S, T
Signal Conditioning
EMI filtering, linearization, and scaling
Cold Junction Compensation
Integrated CJC circuitry
Isolation
Channel-to-channel and channel-to-ground isolation
Terminal Interface
Barrier terminal strips for thermocouple wiring
Storage Temperature
-40 deg C to +85 deg C
Humidity Range
5% to 95% non-condensing
Mounting
Standard Mark VIe rack slot
Compliance
IEC 60584 thermocouple standard
Industrial Control Signal Processing and I/O Density Scaling
The IS230STCIH6A provides thermocouple signal termination and conditioning functions within the GE Mark VIe control architecture. The board receives temperature signals from field thermocouples, applies cold junction compensation, linearization, and filtering, then transfers processed input data through the Mark VIe I/O interface.
The terminal board supports I/O density scaling by integrating 12 temperature measurement channels into a simplex hardware assembly. Firmware flash compatibility depends on the installed GE Mark VIe controller, I/O pack configuration, and system revision.
Channel isolation separates thermocouple measurement circuits from adjacent electrical paths, reducing signal interference during temperature acquisition. The input processing design supports deterministic temperature feedback collection for turbine monitoring and protection logic.
Frequently Asked Questions
Q: How many thermocouple inputs are available on the IS230STCIH6A? A: The IS230STCIH6A provides 12 thermocouple input channels in simplex configuration.
Q: Which thermocouple types are supported by the board? A: The board supports Type E, J, K, S, and T thermocouple sensors.
Q: What function does the CJC circuit perform on the IS230STCIH6A? A: The cold junction compensation circuit corrects reference junction effects during thermocouple temperature measurement processing.
Field Installation Guidelines
Install the IS230STCIH6A in the specified GE Mark VIe rack position and confirm connector engagement before applying system power.
Use compatible thermocouple extension cables and maintain correct polarity between field sensors and terminal connections. Route thermocouple wiring separately from high-current conductors, switching devices, and power supply cables to reduce electromagnetic interference.
Connect cable shields according to cabinet grounding practices. Verify terminal assignments, sensor types, and channel configuration before commissioning.
Inspect terminal blocks, field wiring insulation, and connector conditions during maintenance activities. Avoid unnecessary cable loops and maintain separation between temperature measurement circuits and electrical noise sources.