    Product Overview

    The IS200EGDMH1ADE Exciter Ground Detector Module from GE is designed to detect field leakage resistance in generator circuits within EX2100 excitation systems. It monitors both AC and DC sides and integrates with the EXAM attenuator module for precise ground fault detection.

    Technical Specifications

    Specification Details
    Manufacturer GE (General Electric)
    Model Number IS200EGDMH1ADE
    Product Series EX2100 Excitation
    Category Ground Detector Module
    Input Voltage 24 Vdc
    Technology Surface-mount
    Form Factor Double slot, 6U height
    Dimensions 18 × 12 × 6 cm
    Weight 0.3 kg
    Configuration Modes Simplex or Redundant (C, M1, M2)
    Warranty 12 months from delivery date

    Signal Routing & Master Control

    In redundant setups, three IS200EGDMH1ADE boards operate as Controller (C), Master 1 (M1), and Master 2 (M2). Configuration is managed via program pins on the P2 connector. The active master receives a 50 V square wave signal from DSPX through EISB, which is routed to the EXAM module and applied to the sense resistor.

    Monitoring & Fault Detection

    The module receives voltage signals from EXAM via a nine-conductor cable. It determines ground leakage by analyzing voltage across the sense resistor. Relay control and fiber-optic communication ensure accurate master selection and fault isolation.

    Application & Compatibility

    The IS200EGDMH1ADE is ideal for turbine systems requiring precise ground fault detection and redundancy. It integrates with EPBP, EXAM, DSPX, and EISB components in GE’s EX2100 architecture.

    Specifications

    • Dimensions: 18 × 12 × 6 cm
    • Brand: GE

    Advantages

    • High reliability in industrial environments
    • Supports continuous operation
    • Compatible with major PLC/DCS systems