    Description

    GE DS200SLCCG3AGH LAN Communication Board

    Configured for Ethernet and ARCnet data communication in the GE Mark V Speedtronic turbine control system, the GE DS200SLCCG3AGH (DS200SLCC LAN Communication Board) provides direct physical/electrical execution for controller network interfacing, protocol processing, and diagnostic data exchange between turbine control processors and external systems.

    Suffix Breakdown & Model Matrix

    Model Element Description
    DS200 GE Mark V DS200 hardware series designation
    SLCC LAN Communication Board functional acronym
    G3 Board hardware configuration identifier
    AGH Functional revision and artwork revision designation
    Functional Revision 1 A
    Functional Revision 2 G
    Artwork Revision H

    Hardware Specifications

    Parameter Specification
    Model DS200SLCCG3AGH
    Brand GE
    Origin USA
    Weight 0.55 kg
    Dimensions 200 x 150 x 25 mm
    Operating Temp -30 deg C to +65 deg C
    Power Consumption 24 VDC, 250 mA max
    Board Type LAN Communication Board
    Functional Acronym SLCC
    System Platform GE Mark V Speedtronic Turbine Control System
    Network Interface 10Base-T Ethernet (RJ45)
    Additional Network Interface ARCnet communication
    Supported Protocols TCP/IP, Modbus TCP, GE SRTP, ARCnet
    Processor 32-bit CPU with integrated Ethernet controller
    Firmware Memory 512 KB flash
    SRAM Memory 256 KB
    Data Retention 0.22 F super capacitor, approx. 72 hours
    Isolation 1500 V RMS Ethernet-to-backplane isolation
    Connectors RJ45, 9-pin SUB-D debug port, terminal block
    Indicators Power, Link, Activity, Fault LEDs
    PCB Protection Normal coating

    Deterministic Network Communication

    The DS200SLCCG3AGH manages communication between Mark V controller cores and plant-level control networks through Ethernet and ARCnet interfaces. The onboard communication processor handles protocol conversion, packet processing, and network diagnostics without direct loading of the turbine control processor.

    The board supports industrial network integration through TCP/IP, Modbus TCP, and GE SRTP communication methods. Ethernet communication paths provide deterministic data transfer between controller racks, HMI interfaces, and distributed control system connections.

    Frequently Asked Questions

    Q: What network interfaces are available on the DS200SLCCG3AGH?
    A: The board provides a 10Base-T Ethernet RJ45 interface and ARCnet communication capability for Mark V turbine control network connections.

    Q: What diagnostic information can be monitored from the board?
    A: Four front-panel LEDs indicate power status, network link condition, communication activity, and fault conditions.

    Q: Does the board isolate Ethernet signals from the control backplane?
    A: Yes. The communication interface provides 1500 V RMS isolation between Ethernet circuitry and the Mark V backplane.

    Field Installation Guidelines

    Install the DS200SLCCG3AGH in the designated GE Mark V <C> core rack position and verify connector orientation before insertion. Follow approved cabinet procedures for module removal and installation.

    Use shielded Ethernet cabling where required by the cabinet network design. Route communication cables separately from high-current power wiring and switching circuits to reduce electromagnetic interference.

    Verify Ethernet connections, terminal wiring, and communication configuration settings before startup. Confirm DIP switch settings, network parameters, and protocol assignments according to the approved Mark V system configuration.

    After power application, observe the Power, Link, Activity, and Fault LEDs to confirm communication initialization and network status.

    Specifications

    • Brand: General Electric

    Advantages

    • High reliability in industrial environments
    • Supports continuous operation
    • Compatible with major PLC/DCS systems

    Customer Reviews

    Be the first to write a review
    0%
    (0)
    0%
    (0)
    0%
    (0)
    0%
    (0)
    0%
    (0)
    Send us a message!

    Do you need a large stock? Contact us.

    Collections you may also like

    Recently viewed products

      Login

      Forgot your password?

      Don't have an account yet?
      Create account