Yokogawa ANB10D-410/NDEL ESB Bus Node Unit Configured for signal transmission between Field Control Units and distributed I/O modules in CENTUM...
Read more
Available on working days between 9:00 am to 6:00 pm
Email us: sales2@industriaxplc.com
Available 24/7 for inquiries and support
Description
Yokogawa ANB10D-410/NDEL ESB Bus Node Unit
Configured for signal transmission between Field Control Units and distributed I/O modules in CENTUM VP and CENTUM CS 3000 systems, the Yokogawa ANB10D-410/NDEL (ANB10D ESB Bus Node Unit) provides direct physical and electrical execution of ESB bus communications while supporting redundant power and interface configurations.
Suffix Breakdown &Model Matrix
Code Segment
Description
ANB10D
ESB Bus Node Unit
-4
Dual-redundant ESB bus interface and dual-redundant power supply
1
100 - 120 VAC power input type
0
Basic type
/NDEL
Project-specific option designation as defined by system configuration
HardwareSpecifications
Parameter
Specification
ModelBrand
Yokogawa ANB10D-410/NDEL
Origin
Japan
Weight
Approx. 5.7 kg (excluding I/O modules and cables)
Dimensions
Not specified in provided data
OperatingTemp
0 to 50 degC (operation), -20 to 70 degC (storage)
PowerConsumption
Max. 100 VA at 100 VAC
PowerSupplyVoltage
100 - 120 VAC, 50/60 Hz
I/O Capacity
Up to 8 FIO series I/O modules
Interface Type
Dual-redundant ESB Bus Interface
Power Modules
Dual PW481 power supply modules
Bus Modules
Dual SB401 ESB Bus Interface Modules
Mounting Method
19-inch rack mounting
Ambient Humidity
10 % to 90 % RH, non-condensing
Withstanding Voltage
1500 VAC between power terminals and grounding terminal
Insulation Resistance
20 Mohm minimum at 500 VDC
Channel-to-Channel Isolation Characteristics
The node unit architecture supports isolation strategies commonly applied within distributed process control environments. Channel segregation minimizes electrical coupling between connected I/O circuits, reducing interference propagation through field wiring. When integrated with compatible FIO modules, the platform supports transmission of standard 4-20 mA process signals and communication structures used within HART-enabled instrumentation networks. Compatibility with FOUNDATION Fieldbus and Profibus PA system architectures depends on the connected field interface modules and associated controller configuration.
Frequently Asked Questions
Q: Does the ANB10D-410/NDEL support online replacement of I/O modules? A: The unit is designed to allow I/O module replacement while the node remains operational, subject to the limitations and procedures defined for the installed module type.
Q: How many I/O modules can be installed in one node unit? A: A maximum of 8 FIO series I/O modules can be installed.
Q: What redundancy functions are integrated into the hardware? A: The unit contains dual PW481 power supply modules and dual SB401 ESB bus interface modules, providing redundant power and communication paths.
Field Installation Guidelines
Install the node unit in a properly grounded 19-inch control cabinet.
Separate ESB communication cables from power wiring to reduce electromagnetic coupling.
Terminate cable shields according to plant grounding standards and maintain a single-point shield grounding method where required.
Verify correct seating of PW481 and SB401 modules before energizing the rack.
Maintain ambient conditions within the specified temperature and humidity ranges.
Confirm adequate rack ventilation and unobstructed airflow around installed modules.
Perform insulation and grounding verification before connecting field wiring to associated I/O modules.