Description
Product Description
Overview
The SE4304T01 by EMERSON is a DeltaV digital output (DO) CHARM module designed for 24 V DC inductive load control. It provides reliable, isolated output channels with configurable behavior for both momentary and continuous pulse operations. Its built-in protections and galvanic isolation ensure safe, durable performance in demanding industrial environments.
Key Features
-
Supports 24 V DC inductive loads with continuous 1.0 A output and 2.0 A inrush for short periods (<100 ms)
-
Output voltage range: 4 V DC to 32 V DC
-
Galvanically isolated output channel, factory-tested to 1000 V DC for maximum signal integrity
-
Configurable output behavior: momentary output or continuous pulse output
-
Integrated field circuit protection: 4 A current limiting with thermal shutdown and automatic reset
-
Recommended external fuse at power source for additional safety
-
Low CHARM power consumption: 22 mA max at 24 V DC
-
Minimal heat dissipation: 0.46 W
Technical Specifications
| Specification |
Details |
| Model / Part Number |
SE4304T01 |
| Device Type |
24 V DC Inductive Load CHARM |
| Output Voltage Range |
4 V DC to 32 V DC |
| Continuous Output Current |
1.0 A |
| Inrush Current |
2.0 A (<100 ms) |
| Off-State Leakage Current |
≤1 mA |
| Output Behavior |
Configurable: Momentary or Continuous Pulse |
| Isolation |
Galvanically isolated, 1000 V DC factory-tested |
| Field Circuit Protection |
4 A current limiting, thermal shutdown, automatic reset |
| Recommended Protection |
External fuse at power source |
| CHARM Power Requirement |
22 mA max @ 24 V DC |
| Heat Dissipation |
0.46 W |
Applications
Designed for industrial systems requiring precise, isolated digital outputs. Common applications include process control, chemical plants, oil & gas operations, and power generation systems where inductive load management and output protection are essential.
FAQ
Q: What is the maximum continuous output current?
A: The SE4304T01 supports 1.0 A continuous output with a 2.0 A inrush for less than 100 ms.
Q: How is the module protected against overloads?
A: Integrated 4 A current limiting with thermal shutoff and automatic reset protects the module, while an external fuse is recommended for added safety.
Q: Can the output be configured for different behaviors?
A: Yes, outputs can be set for momentary or continuous pulse operation based on system requirements.