Description
Product Description
Overview
The SE4302T02 from EMERSON DeltaV™ is a digital output (DO) CHARM module engineered for 24 V DC inductive load control. Designed for installation directly in the field, it eliminates the need for traditional marshalling cabinets and complex cross-wiring, reducing installation time, wiring points, and potential failure risks. Its isolated output channels provide reliable performance while protecting downstream circuits.
Key Features
-
Supports 24 V DC inductive loads with 1.0 A continuous output and 2.0 A inrush for under 100 ms
-
Configurable output behavior: momentary output or continuous pulse
-
Galvanically isolated output channel, factory-tested to 1000 V DC
-
Built-in field circuit protection: 4 A current limiting with thermal shutdown and automatic reset
-
Recommended external fuse at power source for additional safety
-
CHARM power requirement: 22 mA max @ 24 V DC
-
Heat dissipation: 0.46 W
-
Direct field installation minimizes wiring and eliminates the need for marshalling cabinets
Technical Specifications
| Specification |
Details |
| Model / Part Number |
SE4302T02 |
| Device Type |
24 V DC Inductive Load CHARM |
| Output Voltage Range |
4 V DC to 32 V DC |
| Continuous Output Current |
1.0 A |
| Inrush Current |
2.0 A (<100 ms) |
| Off-State Leakage Current |
≤1 mA |
| Output Behavior |
Configurable: Momentary or Continuous Pulse |
| Isolation |
Galvanically isolated, factory-tested to 1000 V DC |
| Field Circuit Protection |
4 A current limiting, thermal shutoff, automatic reset |
| Recommended Protection |
External fuse at power source |
| CHARM Power Requirement |
22 mA max @ 24 V DC |
| Heat Dissipation |
0.46 W |
| Installation |
Field-mountable, eliminates marshalling cabinets |
Applications
Ideal for chemical, power generation, and oil & gas industries where space-saving, field-mounted I/O and reliable inductive load control are critical. The module simplifies wiring, reduces contact points, and enhances system reliability.
FAQ
Q: Can this module be used without a marshalling cabinet?
A: Yes, the SE4302T02 is designed for direct field installation, removing the need for a traditional marshalling cabinet.
Q: How is the output protected against overloads?
A: Built-in 4 A current limiting with thermal shutoff protects the module, while an external fuse is recommended at the power source.
Q: What output behaviors are configurable?
A: Outputs can be configured as momentary pulses or continuous pulses depending on the application requirements.