The Emerson KJ3242X1-EA1 (12P3162X022) is an 8-channel analog output module with integrated HART communication, designed for DeltaV M-Series control systems. It converts digital control signals from the DCS into precise 4–20 mA analog outputs, making it ideal for driving valve positioners, actuators, and variable-speed drives. Its HART capability allows simultaneous analog operation and digital device communication for advanced diagnostics and maintenance.
Technical Features
-
Channels: 8 independent outputs sharing a common return
-
Analog Range: 4–20 mA nominal, 0–24 mA full range
-
Resolution: 14-bit minimum digital-to-analog conversion
-
HART Support: Versions 5, 6, and 7 compatible
-
Load Capacity: 0–750 Ω
-
LocalBus Supply: 12.6 VDC at 150 mA (typical)
-
Isolation: Field-to-logic galvanic isolation
-
Operating Temperature: -40 °C to +70 °C
-
Environmental Protection: ISA-S71.04 G3 conformal coating for dust, moisture, and corrosive gas resistance
-
Shock and Vibration: 10 g half-sine 11 ms shock; 1 mm peak-to-peak vibration 2–13.2 Hz, 0.7 g 13.2–150 Hz
-
Humidity: 5–95% non-condensing
Advanced Functionality
-
Integrated HART pass-through for remote device monitoring, configuration, and diagnostics
-
Short circuit protection and open-loop detection
-
Passes device status alerts such as valve or actuator faults to the DeltaV system
-
Hot-swappable with automatic configuration download on insertion
Applications
Designed for high-precision process control in chemical, oil & gas, and energy industries, where real-time diagnostics and remote maintenance reduce downtime and operational risk. Compatible with smart field devices and predictive maintenance tools.
FAQ
Q: Can this module be serviced by users?
A: No. The unit contains no user-serviceable parts. Disassembly is not recommended.
Q: Can the card be removed while the system is powered?
A: Yes, it supports hot-swapping, but follow DeltaV safety guidelines for insertion/removal.
Q: What controllers is this compatible with?
A: DeltaV M-Series controllers and any local I/O carrier slots in the system.
Q: What environmental conditions can it withstand?
A: Extreme industrial conditions including -40 °C to +70 °C, high humidity, vibration, and corrosive airborne contaminants.
Technical Specifications Table
| Feature |
Specification |
| Channels |
8 independent outputs |
| Analog Output |
4–20 mA nominal, 0–24 mA full range |
| Resolution |
14-bit minimum |
| HART Compatibility |
v5, v6, v7 |
| Load Impedance |
0–750 Ω |
| LocalBus Supply |
12.6 VDC, 150 mA typical |
| Isolation |
Field-to-logic galvanic |
| Operating Temperature |
-40 °C to +70 °C |
| Shock |
10 g, half-sine, 11 ms |
| Vibration |
1 mm 2–13.2 Hz, 0.7 g 13.2–150 Hz |
| Humidity |
5–95% non-condensing |
| Environmental Coating |
G3 Conformal (moisture & corrosion protection) |