Description
Product Description
Overview
The KJ3002X1-BG2 is a high-performance power supply designed for the DeltaV™ S-series Distributed Control System (DCS). This modular unit converts 24 VDC field power into precise 12 VDC output for the LocalBus, ensuring uninterrupted operation of controllers and I/O modules. It is optimized for redundant configurations to maintain system reliability in critical applications.
Key Features
-
Redundant Operation (1+1): Supports dual-module setup for hot-standby operation. Failure of one module does not interrupt LocalBus power.
-
Precision Voltage Regulation: Maintains stable 12 VDC output, minimizing EMI and ripple for sensitive digital electronics.
-
Integrated Diagnostics:
-
Front-panel LED indicators (Green = OK, Red = Fault)
-
Software monitoring via DeltaV Diagnostic Explorer for predictive maintenance
-
Robust Environmental Tolerance:
Technical Specifications
| Feature |
Specification |
| Input Voltage |
24 VDC Nominal (Range 18–32 VDC) |
| Output Voltage |
12 VDC LocalBus Power |
| Maximum Load |
13 A typical |
| Efficiency |
>88% at full load |
| Operating Temperature |
-40°C to 70°C (-40°F to 158°F) |
| Shock |
10g, ½ sine wave, 11 ms |
| Vibration |
1 mm peak-to-peak (5–16 Hz), 0.5 g (16–150 Hz) |
| Airborne Contaminants |
ISA-S71.04 Class G3 |
| Humidity |
5–95% non-condensing |
| IP Rating |
IP20 |
| Hazardous Area Rating |
ATEX Zone 2 / Class 1 Div 2 |
| Mounting |
DeltaV S-series Power Carrier |
| Terminal Key Position |
B2 |
Applications
-
Refineries & Petrochemical Plants: Supports high-reliability control loops.
-
Pharmaceutical Batch Processing: Maintains continuous operation to prevent batch loss.
-
Water & Wastewater Treatment: Reliable monitoring and control at remote I/O stations.
Installation and Maintenance Notes
-
Remove field power before module insertion/removal unless using certified dual DC/DC power supplies with inductance ≤23 µH.
-
Only one module may be removed while system power is energized.
-
No user-serviceable parts; disassembly is prohibited.
-
Calibration is not required.
FAQ
Q: Can this module be used in hazardous areas?
A: Yes, it is certified for ATEX Zone 2 and Class 1 Div 2 environments.
Q: What happens if one module in a redundant setup fails?
A: The second module immediately takes over the full load without interrupting LocalBus communication.
Q: Is the KJ3002X1-BG2 compatible with other DeltaV power supplies?
A: It is designed to operate with S-series power carriers and can be integrated with dual DC/DC power supply modules.