Description
Product Description
Overview
The Emerson KJ3001X1-BE1 is an 8-wide horizontal I/O carrier engineered for the DeltaV S-Series Distributed Control System (DCS). It serves as a modular backplane, providing mechanical support, electrical power distribution, and high-speed communication for up to eight traditional S-Series I/O modules. Its snap-in design simplifies installation, maintenance, and system scaling.
Key Features
Integrated Power and Protection
-
Equipped with primary and secondary 24 VDC power buses for field modules.
-
Individual slot fusing isolates faults, preventing a single module from affecting the entire carrier.
High-Speed LocalBus Communication
Rugged Industrial Design
Advanced Reliability and Maintainability
Flexible System Expansion
Technical Specifications
| Feature |
Specification |
| Model Number |
KJ3001X1-BE1 |
| Carrier Capacity |
8 Traditional S-Series I/O Modules |
| Backplane Current |
15 A max |
| Bus Power Distribution |
12 A per bus, 3 A max per slot |
| I/O Module Support |
Digital Inputs/Outputs, Analog Inputs/Outputs |
| Operating Temperature |
-40°C to 70°C (-40°F to 158°F) |
| Storage Temperature |
-40°C to 85°C |
| Humidity |
5% to 95% RH non-condensing |
| Shock |
10 g half-sine, 11 ms |
| Vibration |
1 mm p-p (2–13.2 Hz), 0.7 g (13.2–150 Hz) |
| Protection Rating |
IP20 |
| Mounting |
Horizontal T-type DIN Rail |
| Conformal Coating |
ISA-S71.04-1985 Class G3 |
| Weight |
0.85 kg |
Applications
-
Central I/O backplane for DeltaV S-Series DCS networks
-
High-density process control requiring modular, expandable I/O
-
Continuous and batch control environments with hot-swap maintenance needs
FAQ
Q: Can the carrier be expanded beyond eight I/O modules?
A: Yes, carriers can be connected end-to-end on a T-type DIN rail with carrier extenders to increase I/O capacity.
Q: Are modules hot-swappable?
A: Yes, individual I/O modules can be replaced while the carrier remains powered.
Q: What environments is it rated for?
A: Operating range is -40°C to 70°C, with conformal coating to resist corrosive gases and airborne contaminants.
Q: Does it support multiple I/O types?
A: Yes, it accommodates digital and analog inputs and outputs for flexible deployment.