Description
Product Description
Overview
The DeltaV S-series I/O Module (FM13ATEX0034U) from Emerson is engineered for safe and reliable operation in hazardous environments. Designed to comply with international hazardous area standards, this unit provides robust performance for process automation applications, ensuring compatibility with DeltaV scalable process systems.
Hazardous Area Certification
Installation & Handling
-
Field power must be removed before insertion or removal.
-
The device must not be connected or disconnected while system power is active.
-
A rotary keying system ensures correct terminal block alignment with the I/O card.
Maintenance
Applications
Ideal for process automation in chemical plants, oil & gas facilities, and other hazardous area operations requiring high reliability I/O solutions.
FAQ
Q: Can the unit be replaced while the system is powered?
A: No, system power must be removed before removal or installation.
Q: Does this module require calibration?
A: No, calibration is not necessary.
Q: Which terminal blocks are compatible?
A: Only terminal blocks with matching keying for the I/O card can be used to prevent misconnection.
Q: What are the supported environmental conditions?
A: Operating temperatures from -40 °C to +70 °C, vibration and shock resistant, and non-condensing humidity up to 95%.
Technical Specifications
| Specification |
Details |
| Model |
DeltaV S-series I/O Module (FM13ATEX0034U) |
| Power |
12 VDC, 210 mA |
| Hazardous Area |
ATEX II 3 G Ex nA [ic/nL] IIC Gc, IECEx FMG 13.0015U, FM13ATEX0034U |
| Ambient Temperature |
-40 °C to +70 °C |
| Shock |
10 g, half-sine, 11 ms |
| Vibration |
1 mm peak-to-peak (2–13.2 Hz), 0.7 g (13.2–150 Hz) |
| Humidity |
5–95%, non-condensing |
| Airborne Contaminants |
ISA-S71.04 –1985 Class G3 |
| Maintenance |
No user-serviceable parts, calibration not required |