Description
Product Description
Overview
The KJ4001X1-CC1 from Emerson is a vertical Power/Controller Carrier for DeltaV™ Series 2 systems. Engineered for installations where vertical cabinet space is limited, it provides a secure mounting platform for two controllers and two power supplies. This carrier ensures high-availability operation while managing power distribution and communication between the DeltaV Control Network and downstream I/O modules.
Key Features
Vertical Orientation for Space Efficiency
-
Designed for vertical DIN-rail mounting to optimize cabinet space.
-
Improves airflow and heat dissipation in high-density enclosures.
-
Compatible with vertical wire ducts for neat cable management.
Redundancy and Reliability
-
Dual controller slots enable automatic, bumpless switchover.
-
Dual power slots maintain uninterrupted local bus operation during power module failures.
High-Speed Local Bus
Secure Communication Ports
Industrial-Grade Protection
-
G3 conformal coating shields against moisture and chemical contamination.
-
Operating range from -40°C to +70°C.
-
Includes Carrier ID plug for automatic recognition of slot configuration.
Technical Specifications
| Feature |
Specification |
| Model Number |
KJ4001X1-CC1 |
| Orientation |
Vertical |
| Slot Capacity |
2 Controllers + 2 Power Supplies |
| Mounting |
35mm DIN Rail |
| Input Power |
30 VDC @ 50 mA per channel |
| Local Bus Current |
Up to 8 Amps |
| Network Support |
Redundant Ethernet (802.3) |
| Environmental Protection |
ISA-S71.04-1985 Class G3 |
| Operating Temperature |
-40°C to +70°C |
| Shock Resistance |
10 g half-sine wave, 11 ms |
| Vibration Resistance |
1 mm peak-to-peak (2–13.2 Hz), 0.7 g (13.2–150 Hz) |
| Compatibility |
DeltaV M-Series and S-Series Controllers |
Installation & Maintenance
-
Never insert or remove the carrier while system power is applied.
-
No user-serviceable components; disassembly is prohibited.
-
Factory calibration is permanent; no field adjustments are required.
-
Ensure proper vertical carrier extender cables (KJ4001X1-CK1/CL1) when connecting to I/O carriers.
Applications
-
High-density DeltaV nodes with vertical cabinet orientation
-
Redundant controller setups requiring continuous operation
-
Compact enclosures in industrial environments with vibration or chemical exposure
FAQ
Q: Can I replace a horizontal carrier with this vertical version?
A: Yes, but vertical extender cables are required for proper connection to downstream I/O carriers.
Q: Does this carrier support redundant power and controllers?
A: Yes, it has dual slots for controllers and power modules, enabling bumpless switchover.
Q: What environmental conditions can it operate in?
A: The unit operates reliably from -40°C to +70°C, is vibration-resistant, and is rated for G3-level chemical exposure.