Description
Product Description
Overview
The KJ3223X1-BK1 AI 16-Channel 4–20mA HART Card from Emerson DeltaV is engineered for hazardous environments, providing precise analog input measurement and HART communication for advanced process control. This module supports Zone 2 and Class I Division 2 hazardous areas and offers robust electrical and environmental performance for reliable operation in industrial systems.
Installation and Safety Notes
-
Field power, either local or bussed, must be removed before installation or removal
-
I/O loop assessment required for all energy-limited nodes before connection
-
Module cannot be inserted or removed while system power is energized
-
Rotary keying system ensures correct alignment between I/O cards and terminal blocks
-
Terminal blocks must be keyed to the I/O card they serve
-
Refer to documentation:
Maintenance and Calibration
-
No user-serviceable parts
-
Disassembly is prohibited
-
Calibration is not required
Application Scenarios
Ideal for high-density analog input measurement in hazardous zones, integrating 16 channels of 4–20 mA HART signals into DeltaV systems for chemical processing, energy, and oil & gas facilities.
Frequently Asked Questions (FAQ)
Q: Can this HART card be removed while the system is powered?
A: No. Removal or installation requires the system to be powered down unless the area is non-hazardous.
Q: Is calibration required for operation?
A: No. The module does not require calibration and has no user-serviceable parts.
Q: How does the keying system prevent installation errors?
A: The rotary keying system ensures the terminal block is correctly matched to the corresponding I/O card.
Technical Specifications
| Parameter |
Specification |
| Certifications |
II 3G Ex nA [nL] IIC Gc, II 3G Ex ec [ic] IIC Gc, Class I Div.2 GP. A,B,C,D, Class I Zone 2 AEx/Ex ec [ic] IIC Gc |
| Local Bus Power |
12 VDC, 150 mA |
| Bussed Field Power |
24 VDC, 600 mA |
| Field Circuit |
24 VDC, 30 mA per channel |
| Number of Channels |
16 |
| Signal Type |
4–20 mA HART |
| Operating Temperature |
-40 °C to +70 °C |
| Shock |
10 g, half-sine, 11 ms |
| Vibration |
1 mm peak-to-peak 2–13.2 Hz; 0.7 g 13.2–150 Hz |
| Airborne Contaminants |
ISA-S71.04 Class G3 |
| Relative Humidity |
5–95%, non-condensing |
| Terminal Block Key Position |
A2 |
| Maintenance |
No user-serviceable parts; calibration not required |