Description
Product Overview
The 1C31179G02 (P/N: 1C31179G02) and 1C31227G01 (P/N: 1C31227G01) are specialized S-series FOUNDATION Fieldbus H1 interface cards engineered for the Emerson DeltaV environment. These modules serve as a bridge between the digital control network and field instrumentation, featuring a dual-segment architecture with integrated power conditioning. By merging the H1 controller and power supply into a single footprint, this hardware minimizes cabinet footprint, simplifies wiring complexity, and enables high-resolution device diagnostics alongside synchronized control-in-the-field capabilities.
Detailed Technical Specifications
The following parameters define the electrical and environmental limits for the 1C31179G02 (1C31179G02) and 1C31227G01 (1C31227G01):
-
System Compatibility: Emerson DeltaV S-series I/O subsystem
-
Communication Protocol: FOUNDATION Fieldbus H1 (IEC 61158-2)
-
Segment Density: 2 Independent H1 Channels
-
Integrated Power Supply: Yes (Onboard segment power conditioning)
-
Segment Output Voltage: 28 to 30 VDC (Short-circuit protected)
-
Maximum Output Current: 400mA per segment
-
Field Device Limit: Up to 16 devices per segment (Calculation required based on current draw)
-
Function Block Capacity: 96 Blocks total (64 Fieldbus specific + 32 standard DeltaV)
-
Galvanic Isolation: 1500 VDC (Port-to-system and port-to-port)
-
LocalBus Current Draw: 12 VDC nominal (200mA typical / 300mA peak)
-
Thermal Dissipation: 7.2 Watts
-
Operating Temperature: -40 to +70 degrees Celsius
-
Storage Temperature: -40 to +85 degrees Celsius
-
Relative Humidity Range: 5 percent to 95 percent (Non-condensing)
-
Environmental Rating: ISA-S71.04 G3 (Conformal coating for harsh conditions)
-
Maintenance Features: Support for Hot-Swappable replacement
-
Regulatory Compliance: CE (EMC), FM, and CSA certified
Primary Engineering Applications
The 1C31179G02 (1C31179G02) series is deployed in high-availability industrial sectors:
-
Refining and Chemical Processing: Centralized management of digital fieldbus segments for flow, pressure, and temperature arrays.
-
Asset Management: Seamless integration with AMS Device Manager for predictive maintenance of smart transmitters.
-
Modular Infrastructure: Systems requiring high I/O density with a reduced requirement for external power conditioners and terminal blocks.
Technical FAQ
What distinguishes the 1C31179G02 from the 1C31227G01 variant?
The 1C31227G01 (1C31227G01) is specifically identified as the variant featuring integrated segment power conditioners. This allows the card to directly energize the fieldbus loop. In contrast, the 1C31179G02 (1C31179G02) may be utilized in configurations where external power supplies are already present or required by specific loop designs.
Is redundancy supported for these H1 cards?
Yes. Both the 1C31179G02 (1C31179G02) and 1C31227G01 (1C31227G01) support 1:1 hardware redundancy. When installed in a redundant carrier, the standby module takes over communication immediately upon primary failure to prevent process disruption.
How is device configuration managed?
All connected Fieldbus instruments are configured via DeltaV Control Studio. The interface facilitates the transparent flow of data to AMS (Asset Management Solutions) for deep-level device calibration and health monitoring.