Over 100,000 PLC, DCS, Drive, TSI & MRO Parts In Stock Learn more

Discrete Input Module Schneider Electric 140DDI35310

Discrete Input Module Schneider Electric 140DDI35310

Product form

Schneider Electric 140DDI35310 Discrete Input Module TheSchneider Electric 140DDI35310,also cataloged asthe140DDI35310 Low Voltage DC Discrete Input Module, operates as a... Read more

SKU: 140DDI35310
Country of origin: France

      100% Original and Authentic

    Do you need a large stock? Contact us.

      100% Brand New,Ready to ship

    Do you need a large stock? Contact us.

      Support Refund,7X24h Service

    Support Refund,7X24h Service , Contact us.

      Call us: +86 135 995 07613

    Available on working days between 9:00 am to 6:00 pm

      Email us: sales2@industriaxplc.com

    Available 24/7 for inquiries and support

    Description

    Schneider Electric 140DDI35310 Discrete Input Module

    TheSchneider Electric 140DDI35310,also cataloged asthe140DDI35310 Low Voltage DC Discrete Input Module, operates as a dedicated hardware component for 24 VDC field signal acquisition within Modicon Quantum backplane I/O architecture.

    The module provides 32-channel discrete input scanning with negative (source) logic detection, processing 24 V DC field signals via grouped channel architecture. Signal acquisition is performed through isolated input circuitry with defined voltage thresholds and fast response behavior suitable for high-density digital state monitoring on Quantum systems.

    Suffix Breakdown & Model Matrix

    140 DDI 35310:

    • 140: Modicon Quantum platform identifier
    • DDI: DC Discrete Input
    • 35310: Hardware design / channel configuration variant

    Hardware Specifications

    Parameter Specification
    ModelBrand Schneider Electric 140DDI35310
    Origin France
    Weight 0.3 kg
    PowerConsumption 1.5 W + (0.26 x number of points ON)
    Input Channels 32 discrete inputs
    Input Voltage 24 V DC nominal
    Input Range 19.2...30 V DC
    Logic Type Negative (source)
    Grouping 4 groups of channels
    Input Impedance 2400 Ohm
    Response Time <= 1 ms ON/OFF

    Schneider Electric Backplane I/O Deterministic Scan Behavior

    Within Modicon Quantum architecture, the 140DDI35310 interfaces through a deterministic backplane communication mechanism where input image tables are cyclically updated into PLC memory words. The module maps 32 discrete points into 2 input words, enabling structured data exchange with CPU modules over the rack bus.

    Backplane scan timing is synchronized with system bus cycles, ensuring consistent input state refresh independent of field wiring latency. The module supports high-density channel aggregation while maintaining fixed response time characteristics under full channel load conditions.

    Frequently Asked Questions

    Q: Does the 140DDI35310 support hot-swap insertion in a live Quantum rack?
    A: The module is mechanically compatible with Quantum rack hot insertion design, however field wiring state stability must be maintained during insertion to avoid transient input bit changes.

    Q: What is the maximum backplane load contribution of this module?
    A: The module draws approximately 330 mA from the rack backplane supply, depending on system configuration and bus state activity.

    Q: How is channel grouping structured internally?
    A: The 32 inputs are divided into 4 independent channel groups, each providing isolated signal referencing for structured input scanning and fault segmentation.

    Field Installation Guidelines

    The module shall be installed into a Modicon Quantum rack slot with power removed unless system hot-swap procedures are formally validated. Maintain proper grounding of the rack backplane to ensure stable reference potential for 24 V DC input logic levels.

    Field wiring should use shielded twisted pair conductors where long cable runs are present, with shields terminated at a single-point ground to avoid ground loop formation. Maintain separation between high-voltage conductors and low-level digital input wiring.

    Ensure that input voltage does not exceed 30 V DC continuous or 50 V transient pulse limits to prevent internal input stage stress. Channel grouping should be considered during wiring to simplify fault isolation and maintenance diagnostics.

    Specifications

    • Brand: Schneider Electric

    Advantages

    • High reliability in industrial environments
    • Supports continuous operation
    • Compatible with major PLC/DCS systems