Description
Product Description
Overview
The KJ2005X1-SQ1 is a DeltaV S-Series Smart Quadrant (SQ) Controller engineered for hazardous environments. Designed for reliable operation under extreme temperatures and harsh industrial conditions, this controller meets multiple international certifications for explosive atmospheres and industrial safety.
Certifications & Compliance
Power Requirements
Environmental Specifications
-
Operating Temperature: -40°C to +70°C
-
Shock Resistance: 10 g, ½ sine wave, 11 ms
-
Vibration Resistance: 1 mm peak-to-peak (2–13.2 Hz); 0.7 g (13.2–150 Hz)
-
Airborne Contaminants: ISA-S71.04–1985, Class G3
-
Humidity: 5–95% relative, non-condensing
Installation & Operation Guidelines
-
Installation, removal, and operation must follow DeltaV Zone 2 hazardous area instructions.
-
Network interfaces must remain below 60 VAC or 75 VDC to prevent hazardous conditions.
-
Removal or insertion is only permitted in non-hazardous areas when powered.
Maintenance
Applications
Ideal for chemical plants, oil & gas facilities, and industrial environments requiring precise remote monitoring and control under hazardous conditions.
FAQ
Q: Can this controller be powered while installed in a hazardous area?
A: No, installation or removal must occur in a verified non-hazardous environment.
Q: Does the controller require calibration after installation?
A: No calibration is required; all units are factory-calibrated.
Q: Are there comparable models for different hazardous ratings?
A: DeltaV S-Series offers other SQ controllers rated for Zone 1 and Class I Division 1 environments for higher-risk areas.
Technical Specifications Table
| Specification |
Details |
| Model / Part Number |
KJ2005X1-SQ1 |
| Power Supply |
+5 VDC, 1.4 A |
| Operating Temperature |
-40°C to +70°C |
| Shock |
10 g, ½ sine, 11 ms |
| Vibration |
1 mm P–P (2–13.2 Hz); 0.7 g (13.2–150 Hz) |
| Airborne Contaminants |
ISA-S71.04 Class G3 |
| Humidity |
5–95% non-condensing |
| Certifications |
ATEX II 3G Ex ec IIC Gc, IECEx, UKEX, Class I Div 2 GP A,B,C,D |
| Maintenance |
No user-serviceable parts, factory-calibrated |