Schneider Electric BMXSDO0802 Modicon X80 Discrete Output Module
The Schneider Electric BMXSDO0802, also cataloged as the Modicon X80 discrete output module, operates as a dedicated hardware component for solid-state positive safety logic switching within Modicon automation controller platforms.
Hardware Specifications
Parameter
Specification
Model
BMXSDO0802
Brand
Schneider Electric
Origin
France
Weight
0.12 kg
Dimensions
Not specified
OperatingTemp
Not specified
PowerConsumption
4.4 W maximum power dissipation
Discrete Output Number
8
Discrete Output Type
Solid state (Not isolated)
Discrete Output Logic
Positive
Discrete Output Voltage
24 V DC (19...30 V DC)
Discrete Output Current
0.5 A nominal
Current per Channel
0.625 A
Maximum Current per Module
10 A
Maximum Leakage Current
0.5 mA at state 0
Maximum Voltage Drop
<1.2 V at state 1
Insulation Resistance
> 10 MOhm at 500 V DC
Response Time on Output
1.2 ms
Paralleling of Outputs
Yes (2 maximum)
Typical Current Consumption
264 mA at 3.3 V DC, 15 mA at 24 V DC
MTBF Reliability
401208 H
Output Overload Protection
Current limiter and electronic circuit breaker (1.5 In < Id < 2 In)
Output Overvoltage Protection
Transil diode
Output Short-Circuit Protection
External 2 A fuse required
Reverse Polarity Protection
Reverse mounted diode
Voltage Detection Threshold
< 14 V DC (sensor fault), > 18 V DC (sensor OK)
Maximum Tungsten Load
6 W
Switching Frequency
0.5/LI^2 Hz
Load Impedance Ohmic
<= 48 Ohm
Status LED Indicators
1 LED green (RUN), 1 LED green per channel (diagnostic), 1 LED red (ERR), 1 LED red (I/O)
Backplane Bus Communication Velocity
The module interfaces directly with the Modicon X80 backplane, utilizing high-speed bus communication synchronization to update the status of the 8 solid-state outputs. This deterministic bus integration minimizes internal propagation latency and ensures synchronous logic execution matching the main processor scan cycle.
Frequently Asked Questions
Q: What is the maximum configuration allowed when paralleling outputs on this module?
A: A maximum of 2 outputs can be connected in parallel to handle higher current loads, provided that the total current draw does not exceed the overall module limit of 10 A.
Q: What mechanisms handle overcurrent and short-circuit faults on the channels?
A: The module utilizes an internal current limiter and an electronic circuit breaker calibrated between 1.5 In and 2 In for overload states. Short-circuit conditions require the installation of an external 2 A fuse per specified guidelines.
Field Installation Guidelines
Install a mandatory 2 A external fast-acting fuse in series with the output channels to ensure proper short-circuit protection and prevent physical damage to the solid-state circuitry.
Route all 24 V DC field wiring away from high-voltage AC cables to minimize cross-talk and electromagnetic interference on the non-isolated positive logic channels.
Verify that the total current load across all 8 channels does not exceed the 10 A maximum rating under peak operational conditions to prevent thermal overstress.