Yokogawa ATI3S Temperature Transmitter Module
TheYokogawa ATI3S-00also cataloged astheATI3Stemperature transmitter module, operates as a dedicated hardware component for isolated analog signal conversion within CENTUM VP and CENTUM CS 3000 FIO subsystem architectures. TheYokogawa ATI3S-00(ATI3Stemperature transmitter module) provides direct physical/electrical execution of thermocouple, RTD, mV, and resistance signal acquisition into a 4-20 mA HART loop interface.
Suffix Breakdown & Model Matrix
ATI3S-00: Standard configuration without extended environmental or protection options
No additional functional suffix definition provided in source data
Base series ATI3S: Field I/O temperature transmitter interface family
Hardware Specifications
Parameter
Specification
ModelBrand
Yokogawa ATI3S-00
Origin
Japan
Weight
Approx. 1.2 kg
Dimensions
Not specified
OperatingTemp
-40 to 85 degC (operation), -50 to 100 degC (storage)
PowerConsumption
Not specified
Input Types
Thermocouple (K, E, J, T, N, R, S, B), RTD (Pt100, JPt100), mV, resistance
Measurement Range
-200 to 1820 degC (sensor dependent)
Output Signal
4-20 mA with HART protocol
Accuracy
+/-0.1 percent of reading or +/-0.25 degC
Response Time
<= 250 ms
Stability
+/-0.1 percent of span per year
Housing
IP66 / IP67 aluminum alloy
Yokogawa 4-20 mA HART Loop and Channel Signal Conditioning Characteristics
The ATI3S architecture implements analog-to-current conversion using a 4-20 mA loop structure with HART digital overlay communication. Within Yokogawa FIO systems, signal acquisition from thermocouples and RTDs is processed with cold junction compensation (CJC) handling integrated at the transmitter level.
Channel-level behavior is defined by the following electrical characteristics:
4-20 mA loop current scaling for primary process variable transmission
HART protocol superimposed digital communication on analog current loop
Sensor linearization executed within transmitter firmware domain
Input multiplexing across thermocouple and RTD signal classes
Environmental drift compensation via internal stability calibration model
No FOUNDATION Fieldbus or Profibus PA implementation is defined for this module.
Frequently Asked Questions
Q1: Does ATI3S support direct thermocouple cold junction compensation externally? A1: No external CJC module is required. Cold junction compensation is handled internally within the transmitter signal processing stage.
Q2: Can ATI3S output be used in non-HART 4-20 mA loops? A2: Yes. The analog 4-20 mA signal is primary. HART is superimposed and does not block standard current loop operation.
Q3: Does the module support resistance and mV inputs simultaneously? A3: Input type selection is configuration-based. Only one measurement mode is active per channel configuration instance.
Field Installation Guidelines
Maintain correct polarity on 4-20 mA loop terminals to prevent transmitter non-start condition
Use shielded twisted pair cable for thermocouple and RTD input lines
Ground cable shield at single point within control cabinet to avoid ground loop formation
Avoid routing signal cables parallel to high-voltage switching conductors
Ensure IP66/IP67 housing sealing integrity is preserved during enclosure installation
Verify sensor type configuration matches wiring input before loop energization