    Description

    Yokogawa AAB841-S00 Analog Input Module

    Configured for analog signal acquisition in CENTUM VP and CENTUM CS 3000 distributed control systems, the Yokogawa AAB841-S00 (AAB841 Analog Input Module) provides direct electrical interfacing between field instrumentation and control processors via 4–20 mA and 1–5 V DC input channels.

    Hardware Specifications

    Parameter Specification
    Model Brand Yokogawa AAB841-S00
    Origin Japan
    Weight 0.35 kg
    Dimensions 12.5 cm x 10.5 cm x 3.5 cm
    Operating Temp 0 to 55 degC
    Power Consumption Max. 300 mA @ 5 VDC
    Number of Channels 8, isolated
    Input Signals 4–20 mA DC, 1–5 V DC
    Input Impedance 250 ohm (current), ≥1 Mohm (voltage)
    Withstanding Voltage 1500 V AC (signal–system), 500 V AC (channel–channel)
    Accuracy ±0.1% of full scale
    Data Refresh Cycle 100 ms
    Connection Type Pressure clamp terminal or dedicated cable

    Channel-to-Channel Isolation Characteristics

    Channel-to-channel isolation eliminates ground loops and suppresses common-mode noise between input circuits. Each channel employs independent signal conditioning paths referenced to isolated internal potential planes. Isolation withstand ratings are maintained per Yokogawa FCS design standards to prevent cross-circuit fault propagation during transient overvoltage events.

    Frequently Asked Questions

    Q: Does the AAB841-S00 support hot-swapping?

    A: Yes, when installed in a dual-redundant I/O node configuration, the module can be replaced online without interrupting control execution.

    Q: What is the backplane current load for this module?

    A: Maximum backplane current draw is 300 mA at 5 VDC system power.

    Q: Are input channels galvanically isolated from the system bus?

    A: Yes, the module provides 1500 V AC isolation between input signals and the system side.

    Field Installation Guidelines

    Mount the module in designated I/O slot positions within the Yokogawa FCS or node unit. Use shielded twisted-pair cabling for all analog input wiring. Connect shield drains to the common ground bus at the cabinet entry point only. Ensure torque specifications on pressure clamp terminals meet Yokogawa-recommended values (typically 0.5 N·m). Verify input polarity before applying power. Perform gap voltage checks after installation to confirm correct signal referencing.

    Specifications

    • Brand: Yokogawa

    Advantages

    • High reliability in industrial environments
    • Supports continuous operation
    • Compatible with major PLC/DCS systems

    Customer Reviews

    Be the first to write a review
    0%
    (0)
    0%
    (0)
    0%
    (0)
    0%
    (0)
    0%
    (0)
    Send us a message!

    Do you need a large stock? Contact us.

    Collections you may also like

    Recently viewed products

      Login

      Forgot your password?

      Don't have an account yet?
      Create account