    Yokogawa ALU4*D Modular I/O System

    The Yokogawa AAI141, also cataloged as the ALU4D* Analog Input Module, operates as a dedicated hardware component for 4-20 mA DC signal acquisition within Yokogawa CENTUM VP and CENTUM CS 3000 distributed control systems.

    Hardware Specifications

    Parameter Specification
    Model Brand Yokogawa ALU4*D Series
    Origin Japan
    Weight 0.2 kg
    Dimensions Standard DIN-rail mount modular width
    Operating Temp 0 to 60 degC
    Power Consumption 310 mA @ 5 VDC, 450 mA @ 24 VDC
    Number of Input Channels 16, non-isolated
    Input Signal Range 4 to 20 mA DC, 1 to 5 V DC, -10 to 10 V DC
    Allowable Common Mode Voltage ±1 V or less
    Input Resistance (Power ON) 400 Ohm @ 20 mA, 1000 Ohm @ 4 mA, 1 MOhm or larger
    Input Resistance (Power OFF) 500 kOhm or larger, 340 kOhm or larger, 660 kOhm or larger
    Accuracy ±16 uA, ±4 mV, ±20 mV
    Data Update Period 10 ms
    Step Response Time 100 ms
    Transmitter Power Supply 14.8 V or higher @ 20 mA, 26.4 V or less @ 0 mA
    Output Current Limit 27 mA

    4-20 mA HART Loop Protocol Handling

    Channel-level configuration pins define 2-wire or 4-wire transmitter excitation sourcing. The module supplies a regulated 24 VDC loop power rail to active field devices. The input circuitry tolerates a maximum common mode voltage of ±1 V DC. Transmitter supply voltage regulation maintains output above 14.8 V DC under full 20 mA load conditions. The input resistance profile scales inversely with current magnitude, presenting 400 Ohm at 20 mA and rising to 1000 Ohm at 4 mA. This characteristic requires verification against field transmitter load drive capability specifications.

    Frequently Asked Questions

    Q: Does the ALU4*D support hot-swapping while the CENTUM VP node is operational?

    A: Yes, the module supports online replacement. The system backplane maintains communication integrity during the exchange procedure. Verify that the replacement unit matches the existing I/O assignment configuration prior to insertion.

    Q: What is the impact of non-isolated channel design on wiring practices?

    A: All 16 input channels share a common reference potential. Field wiring must ensure that external sensor grounds do not introduce ground loops exceeding the ±1 V common mode limit. Use isolated barrier devices if field device grounding conflicts occur.

    Q: How does temperature drift affect calibration intervals?

    A: Accuracy drift is specified at ±16 uA per 10 degC. For applications requiring sustained high precision, perform field calibration checks when ambient temperature variations exceed 30 degC from the initial calibration environment.

    Field Installation Guidelines

    Mount the module onto the dedicated Yokogawa baseplate assembly. Use the pressure clamp terminal blocks for field wiring termination. Ensure that the shield drain wire connects directly to the designated earth ground point on the baseplate to maintain signal integrity. Torque terminal screws to the manufacturer-specified value to prevent thermal expansion loosening. Verify that the KS cable or MIL connector routing avoids parallel runs with high-voltage power conductors to minimize electromagnetic interference pickup.

    Specifications

    • Brand: Yokogawa

    Advantages

    • High reliability in industrial environments
    • Supports continuous operation
    • Compatible with major PLC/DCS systems

    Customer Reviews

    Be the first to write a review
    0%
    (0)
    0%
    (0)
    0%
    (0)
    0%
    (0)
    0%
    (0)
    Send us a message!

    Do you need a large stock? Contact us.

    Collections you may also like

    Recently viewed products

      Login

      Forgot your password?

      Don't have an account yet?
      Create account