    Yokogawa AEA4D-01 Terminal Board

    The Yokogawa AEA4D-01, also cataloged as the AEA4D Terminal Board, operates as a dedicated hardware component for analog signal interfacing within CENTUM and ProSafe-RS systems. It provides physical termination and routing for field instruments to Yokogawa FIO modules, supporting both single and dual-redundant I/O configurations.

    Hardware Specifications

    Parameter Specification
    ModelBrand Yokogawa AEA4D-01
    Origin Japan
    Weight 1.5 kg
    Dimensions Dual-row vertical terminal block, standard panel mount
    OperatingTemp -20 degC to +70 degC
    AmbientHumidity 5% to 95% RH (non-condensing)
    TerminalScrewType M4 Screw Terminals
    ChannelCapacity 16 channels (8 points x 2 blocks)
    SignalConfiguration Single or dual-redundant analog
    InsulationResistance ≥ 100 MOhm at 500 VDC
    WithstandingVoltage 500 VAC for 1 minute
    ConnectionCable Yokogawa KS1 signal cable
    MountingMethod 19-inch rack or panel with 4 x M5 screws

    Process Control DCS Features

    The AEA4D-01 supports 4-20 mA HART loop protocol and maintains channel-to-channel isolation for noise suppression. Cold junction compensation (CJc) is applied internally to reduce temperature-induced drift. Dual-redundant port architecture enables uninterrupted signal routing during FIO module replacement or failure, maintaining DCS operational integrity.

    Frequently Asked Questions

    Q: VnA: Can the AEA4D-01 support hot-swap of FIO modules?
    A: Yes, field wiring remains undisturbed, and module replacement can be conducted without powering down the I/O rack.

    Q: VnA: What is the maximum cable length for connecting field instruments?
    A: Standard Yokogawa KS1 cable specifications should be followed; length is determined by analog signal attenuation and noise margin.

    Q: VnA: Is surge protection integrated?
    A: No, the standard suffix (-0/-1) models are supplied without surge absorbers; external protection must be implemented if required.

    Field Installation Guidelines

    • Mount the terminal board on a standard 19-inch rack or panel using 4 x M5 screws.
    • Connect field instrument cables using M4 screw terminals ensuring torque per industrial standards to maintain gas-tight contact.
    • Maintain separation of analog signal cables from power lines to prevent electromagnetic interference.
    • Ground shielding at one end only to avoid ground loops.
    • Verify dual-redundant port connections when configuring for hot-standby operation.
    • Avoid mechanical stress on cables during installation to prevent signal degradation.

    Specifications

    • Brand: Yokogawa

    Advantages

    • High reliability in industrial environments
    • Supports continuous operation
    • Compatible with major PLC/DCS systems

    Customer Reviews

    Be the first to write a review
    0%
    (0)
    0%
    (0)
    0%
    (0)
    0%
    (0)
    0%
    (0)
    Send us a message!

    Do you need a large stock? Contact us.

    Collections you may also like

    Recently viewed products

      Login

      Forgot your password?

      Don't have an account yet?
      Create account