Over 100,000 PLC, DCS, Drive, TSI & MRO Parts In Stock Learn more

ADV551-P00/D5A00 Yokogawa Digital Output Module-32 Channels

ADV551-P00/D5A00 Yokogawa Digital Output Module-32 Channels

Product form

Yokogawa ADV551-P00/D5A00 Digital Output Module Configured for 24 VDC transistor signal switching in CENTUM and related Yokogawa control platforms, the... Read more

SKU: ADV551-P00/D5A00
Country of origin: JAPAN

      100% Original and Authentic

    Do you need a large stock? Contact us.

      100% Brand New,Ready to ship

    Do you need a large stock? Contact us.

      Support Refund,7X24h Service

    Support Refund,7X24h Service , Contact us.

      Call us: +86 135 995 07613

    Available on working days between 9:00 am to 6:00 pm

      Email us: sales2@industriaxplc.com

    Available 24/7 for inquiries and support

    Description

    Yokogawa ADV551-P00/D5A00 Digital Output Module

    Configured for 24 VDC transistor signal switching in CENTUM and related Yokogawa control platforms, the Yokogawa ADV551-P00/D5A00 (ADV551 Digital Output Module) provides direct physical/electrical execution for 32-channel discrete output transmission. The module supports current sink output architecture with isolated channel grouping, external 24 VDC supply operation, and ON/OFF pulse output handling through dedicated terminal and MIL cable interfaces.

    Suffix Breakdown & Model Matrix

    Code Segment Specification
    ADV551 32-channel digital output module
    -P00 Basic type without additional functional expansion
    /D5A00 KS cable interface adapter included

    Hardware Specifications

    Parameter Specification
    Model ADV551-P00/D5A00
    Brand Yokogawa
    Product Type Digital Output Module
    Origin France
    Output Channels 32 channels
    Output Type Current sink transistor output
    Rated Applied Voltage 24 VDC
    Load Voltage 24 VDC, 50 mA/channel
    External Power Supply Voltage 20.4 to 26.4 VDC
    Maximum Load Current 100 mA/channel at 26.4 VDC
    Output ON Voltage 2 VDC maximum
    OFF-State Leak Current 0.1 mA
    Withstanding Voltage 2 kVAC for 1 minute
    Inter-Common Isolation 500 VAC for 1 minute per 16-channel group
    Output Response Time 3 ms
    Pulse Width Range 8 ms to 7200 s
    Pulse Width Resolution 8 ms
    Delay Tolerance Maximum 1 ms ON/OFF transition delay
    External Connection Pressure clamp terminal, AKB331 cable, MIL connector cable
    Power Consumption 700 mA at 5 VDC, 60 mA external supply
    Dimensions 3.2 cm x 10.6 cm x 13 cm
    Weight 0.2 kg to 0.3 kg

    Channel-to-Channel Isolation Characteristics

    The ADV551-P00/D5A00 implements grouped electrical isolation between output signal circuits and internal system circuitry. Isolation withstand capability is specified at 2 kVAC for 1 minute between output signals and the control system side. Separate commons are partitioned in 16-channel groups with 500 VAC isolation separation.

    The module operates using current sink transistor outputs intended for external 24 VDC field loads. OFF-state leakage is limited to 0.1 mA, reducing unintended field-side energization during inactive states. Output transition handling supports pulse-driven discrete control sequences with programmable timing resolution beginning at 8 ms intervals.

    Frequently Asked Questions

    Q: Does the ADV551-P00/D5A00 support hot swapping during controller operation?
    A: The provided specification does not explicitly define online insertion or hot-swap capability. Standard practice is to isolate field power and follow Yokogawa controller maintenance procedures before module replacement.

    Q: What field wiring interfaces are supported by this module?
    A: The module supports pressure clamp terminal connections, dedicated AKB331 cable assemblies, and MIL connector cable interfaces.

    Q: How are output commons electrically separated?
    A: Output commons are isolated in groups of 16 channels with 500 VAC withstand separation between commons.

    Field Installation Guidelines

    • Verify external supply voltage remains within 20.4 to 26.4 VDC before energizing field outputs.
    • Route output wiring separately from analog signal cables to minimize inductive switching interference.
    • Terminate cable shield grounding at a single control cabinet grounding point to avoid circulating ground current loops.
    • Confirm field load current does not exceed 100 mA per channel under maximum supply conditions.
    • Maintain correct polarity on current sink output circuits during terminal installation.
    • Inspect pressure clamp terminal retention force after field vibration exposure or maintenance activity.

    Specifications

    • Brand: Yokogawa

    Advantages

    • High reliability in industrial environments
    • Supports continuous operation
    • Compatible with major PLC/DCS systems