ABB TB806 3BSE008536R1 ModuleBus Extension Cable Adaptor Configured for ModuleBus signal extension connection in ABB S800 I/O systems, the ABB...
Read more
Configured for ModuleBus signal extension connection in ABB S800 I/O systems, the ABB TB806 3BSE008536R1 (TB806 ModuleBus Extension Cable Adaptor) provides direct physical interface adaptation between ModuleBus segments through a D-SUB 25 male connector.
Hardware Specifications
Parameter
Specification
Model
TB806 3BSE008536R1
Brand
ABB
Product Type
ModuleBus Extension Cable Adaptor
Origin
Sweden
Weight
0.1 kg
Dimensions
12.7 x 5.1 x 5.1 cm
Operating Temp
0 to +55 deg C
Storage Temperature
-25 to +70 deg C
Humidity Range
RH 5 to 95 %
Power Consumption
Passive interface component, no external power supply required
Mechanics
S800
Connector Type
D-SUB 25 male
Tariff Code
8537101190
Hazardous Location
C1 Div 2 cULus, C1 Zone 2 cULus, ATEX Zone 2
Marine Certification
ABS, BV, DNV, LR
Pollution Degree
Degree 2, IEC 60664-1
Corrosion Protection
ISA-S71.04: G3
ABB S800 ModuleBus Interface Characteristics
The TB806 operates as a passive ModuleBus interface adapter within ABB S800 I/O configurations. Therefore, it supports physical connection extension between compatible ModuleBus components while maintaining the electrical characteristics of the communication path.
In addition, ABB S800 architecture depends on defined backplane and ModuleBus communication structures. The TB806 provides the required connector conversion function without adding firmware processing or active communication control.
Furthermore, the adaptor supports industrial installation requirements with specified hazardous location approvals and environmental protection classifications. The unit maintains compatibility with ABB ModuleBus extension arrangements where D-SUB 25 male interfaces are required.
Frequently Asked Questions
Q: Does the ABB TB806 3BSE008536R1 require an external power supply? A: No. The TB806 is a passive ModuleBus extension cable adaptor and does not require an independent power input.
Q: What connector interface does the TB806 provide? A: The TB806 provides a D-SUB 25 male connector interface for ModuleBus extension connection within ABB S800 configurations.
Q: Can the TB806 be installed in hazardous areas? A: Yes. The listed certifications include C1 Div 2 cULus, C1 Zone 2 cULus, and ATEX Zone 2 approval classifications.
Field Installation Guidelines
Install the TB806 according to ABB S800 ModuleBus system documentation and approved wiring practices.
Verify connector orientation before inserting the D-SUB interface to prevent mechanical damage.
Maintain proper cable routing and separate ModuleBus wiring from high-voltage power conductors.
Use appropriate shielding and grounding methods according to the installation environment.
Confirm environmental conditions remain within the specified operating temperature and humidity limits.
Inspect connectors for contamination, corrosion, or mechanical stress before system commissioning.