Over 100,000 PLC, DCS, Drive, TSI & MRO Parts In Stock Learn more

ABB Advant S800 I/O TU830V1 Extended Module Termination Unit

ABB Advant S800 I/O TU830V1 Extended Module Termination Unit

Product form

ABB TU830V1 Extended Module Termination Unit Configured for field wiring termination, process voltage distribution, and ModuleBus signal routing in the... Read more

SKU: TU832
Country of origin: Sweden

      100% Original and Authentic

    Do you need a large stock? Contact us.

      100% Brand New,Ready to ship

    Do you need a large stock? Contact us.

      Support Refund,7X24h Service

    Support Refund,7X24h Service , Contact us.

      Call us: +86 153 9592 3051

    Available on working days between 9:00 am to 6:00 pm

      Email us: sales2@industriaxplc.com

    Available 24/7 for inquiries and support

    Description

    ABB TU830V1 Extended Module Termination Unit

    Configured for field wiring termination, process voltage distribution, and ModuleBus signal routing in the ABB S800 I/O system, the ABB TU830V1 (TU830 Extended Module Termination Unit) provides the physical interface between field circuits and the I/O module.

    Hardware Specifications

    Parameter Specification
    Model TU830V1
    Base Model TU830
    Brand ABB
    Product Type Extended Module Termination Unit (MTU)
    Part Number / Catalog Code 3BSE013234R1
    System Compatibility ABB S800 I/O system
    I/O Channels Up to 16
    Maximum Rated Voltage 50 V
    Maximum Rated Current per Channel 2 A
    Process Voltage Connections 2 individually isolated groups, UP1 and UP2
    Group Fuse Rating 6.3 A time-lag fuse, 5 x 20 mm
    ModuleBus Function Distributes ModuleBus and shifts position signals for I/O module addressing
    Wire Size, Solid 0.2 - 4 mm2
    Wire Size, Stranded 0.2 - 2.5 mm2, 24 - 12 AWG
    Terminal Tightening Torque 0.5 - 0.6 Nm
    Mechanical Keying 36 coding combinations
    Mounting Standard DIN rail
    Grounding Built-in system grounding mechanism
    Operating Temp 0 deg C to 55 deg C

    ModuleBus and I/O Density

    The TU830V1 distributes ModuleBus communication through the S800 I/O termination structure. It also shifts outgoing position signals so that the connected I/O module receives the corresponding hardware position address.

    Furthermore, the MTU supports up to 16 I/O channels while maintaining separate process voltage groups. The two groups provide individual isolation and fuse protection for connected field circuits.

    The 36 available mechanical coding combinations restrict incompatible I/O module insertion. Therefore, the selected coding must correspond to the intended I/O module before installation.

    Frequently Asked Questions

    Q: Does the TU830V1 provide I/O signal conversion?

    A: No. The TU830V1 functions as a termination and distribution unit. The connected S800 I/O module performs the actual signal processing.

    Q: What process voltage protection does the TU830V1 provide?

    A: The unit provides two individually isolated process voltage groups. Each group uses a 6.3 A time-lag fuse according to the supplied specifications.

    Q: Can the TU830V1 support more than 8 I/O channels?

    A: Yes. The supplied data specifies a maximum of 16 I/O channels for the TU830V1.

    Field Installation Guidelines

    • Mount the TU830V1 securely on the specified DIN rail before connecting field wiring.
    • Verify the mechanical coding before inserting the associated S800 I/O module.
    • Separate process voltage wiring from communication and low-level signal wiring where cabinet design permits.
    • Maintain correct polarity and terminal identification for every field circuit.
    • Tighten field terminals to 0.5 - 0.6 Nm where the supplied specification applies.
    • Select conductor sizes within the stated 0.2 - 4 mm2 solid or 0.2 - 2.5 mm2 stranded range.
    • Connect the grounding arrangement according to the S800 installation design and cabinet grounding scheme.
    • Verify both process voltage groups independently before energizing the connected I/O circuits.
    • Inspect fuse installation and confirm that the installed fuse type matches the specified protection arrangement.
    • Do not exceed 50 V rated voltage or 2 A rated current per I/O channel.

    Specifications

    • Brand: ABB

    Advantages

    • High reliability in industrial environments
    • Supports continuous operation
    • Compatible with major PLC/DCS systems

    Customer Reviews

    Be the first to write a review
    0%
    (0)
    0%
    (0)
    0%
    (0)
    0%
    (0)
    0%
    (0)
    Send us a message!

    Do you need a large stock? Contact us.

    Collections you may also like

    Recently viewed products