Yokogawa AAI135-H00/K4A00 Analog Input Module TheYokogawa AAI135-H00/K4A00,also cataloged as theAAI135Analog Input Module, operates as a dedicated hardware component for 4-20...
Read more
Available on working days between 9:00 am to 6:00 pm
Email us: sales2@industriaxplc.com
Available 24/7 for inquiries and support
Description
Yokogawa AAI135-H00/K4A00 Analog Input Module
TheYokogawa AAI135-H00/K4A00,also cataloged as theAAI135Analog Input Module, operates as a dedicated hardware component for 4-20 mA current signal acquisition within DCS analog input processing networks. Configured for field current loop termination and HART superimposed digital communication decoding, theYokogawa AAI135-H00/K4A00(AAI135Analog Input Module) provides direct physical/electrical execution.
Suffix Breakdown & Model Matrix
AAI135: Base model, 8-channel isolated 4-20 mA analog input module
H00: Basic configuration set with HART communication support enabled via module interface
500 V AC (input-system, 1 min); 500 V AC (channel-channel, 1 min)
Input Resistance
290 ohm (20 mA, power ON) to 450 ohm (4 mA, power ON); >= 500 k ohm (power OFF)
Accuracy
+/- 16 uA
Communication
HART protocol overlay supported
Process Signal Conditioning and HART Loop Handling
The module implements HART protocol superimposition on 4-20 mA analog loops, enabling simultaneous analog measurement and digital field device communication without signal separation hardware. Channel-to-channel galvanic isolation reduces inter-channel electrical coupling under mixed-loop termination conditions, maintaining stable current acquisition across all 8 inputs in dense I/O configurations.
Frequently Asked Questions
Q: Does the module support hot-swap replacement under live backplane power? A: Hot-swap capability depends on system rack design; electrical isolation is maintained per channel, but backplane behavior is system-defined.
Q: What is the effect of HART communication on 4-20 mA measurement accuracy? A: HART signal is superimposed at low amplitude frequency; analog current measurement remains within specified +/- 16 uA accuracy band.
Q: Can unused channels be left open-circuit? A: Open channels should follow termination guidelines to avoid noise pickup; input resistance in power OFF state is >= 500 k ohm.
Field Installation Guidelines
Maintain correct polarity for each 4-20 mA loop connection at terminal interface
Use shielded twisted pair wiring for all analog input channels
Ground cable shields at a single-point earth reference to avoid ground loop currents
Ensure KS cable interface adapter ATK4A-00 is fully seated before energizing system
Avoid routing analog input wiring parallel to high-voltage or switching power lines
Verify channel isolation integrity before commissioning multi-loop installations