Over 100,000 PLC, DCS, Drive, TSI & MRO Parts In Stock Learn more

330101-00-24-10-02-05 3300 XL 8 mm Proximity Probe | Bently Nevada

330101-00-24-10-02-05 3300 XL 8 mm Proximity Probe | Bently Nevada

Product form

Bently Nevada 330101-00-24-10-02-05 3300 XL 8 mm Proximity Probe The Bently Nevada 330101-00-24-10-02-05, also cataloged as the 330101 3300 XL... Read more

SKU: 330101-00-24-10-02-05
Country of origin: USA

      100% Original and Authentic

    Do you need a large stock? Contact us.

      100% Brand New,Ready to ship

    Do you need a large stock? Contact us.

      Support Refund,7X24h Service

    Support Refund,7X24h Service , Contact us.

      Call us: +86 135 995 07613

    Available on working days between 9:00 am to 6:00 pm

      Email us: sales2@industriaxplc.com

    Available 24/7 for inquiries and support

    Description

    Bently Nevada 330101-00-24-10-02-05 3300 XL 8 mm Proximity Probe

    The Bently Nevada 330101-00-24-10-02-05, also cataloged as the 330101 3300 XL 8 mm Proximity Probe, operates as a dedicated eddy-current sensing element for radial and axial shaft displacement measurement within Bently Nevada 3300 monitoring systems.

    Hardware Specifications

    Parameter Specification
    Model Brand Bently Nevada
    Origin USA
    Weight 0.05 kg
    Dimensions 1.5 x 1.3 x 116 cm
    Operating Temp -40 to +120 degC
    Power Consumption Passive sensor, no external power
    Thread Type 3/8-24 UNF
    Unthreaded Length 0.0 in
    Overall Case Length 2.4 in
    Total Length 1.0 m (3.3 ft)
    Connector Type Miniature coaxial ClickLoc connector
    Agency Approvals CSA, ATEX, IECEx

    Eddy-Current Probe Scaling and Gap Voltage Validation

    Probe scale factor is factory calibrated at 7.87 mV/μm (200 mV/mil) ±5% across the linear range. Target gap voltage for installation verification is -10.0 VDC relative to the driver’s internal reference. Rotor dynamic measurements require maintaining probe clearance within the linear region to prevent signal saturation or cross-talk interference between adjacent probes.

    Frequently Asked Questions

    Q: Can this probe be used with 3300 XL extension cables longer than 5 meters?

    A: No. Total system length must not exceed the specified maximum cable run to maintain impedance matching and signal integrity.

    Q: Is hot-swapping supported during machinery operation?

    A: No. System power should be removed before connecting or disconnecting the probe assembly to avoid transient overvoltages.

    Q: What is the minimum bend radius for the coaxial cable?

    A: Maintain a bend radius of at least 25 mm to prevent dielectric deformation and signal loss.

    Field Installation Guidelines

    Install probe tip perpendicular to the target surface with full thread engagement into the mounting bracket. Use proper torque to secure the probe without inducing mechanical stress on the tip. Ground the shield of the coaxial cable to the monitor chassis earth terminal only at one end to minimize ground loops. Route signal cables separately from high-voltage power wiring to reduce electromagnetic interference. Verify gap voltage after installation using a calibrated voltmeter referenced to the monitor’s common.

    Specifications

    • Brand: Bently Nevada

    Advantages

    • High reliability in industrial environments
    • Supports continuous operation
    • Compatible with major PLC/DCS systems