3300/16-12-01-02-01-02-00 Bently Nevada Dual Vibration Monitor

3300/16-12-01-02-01-02-00 Bently Nevada Dual Vibration Monitor

Product form

Bently Nevada 3300/16-12-01-02-01-02-00 Dual Vibration Monitor Configured for dual-channel radial vibration and gap voltage processing in the Bently Nevada 3300... Read more

SKU: 3300/16-12-01-02-01-02-00
Country of origin: USA

      100% Original and Authentic

    Do you need a large stock? Contact us.

      100% Brand New,Ready to ship

    Do you need a large stock? Contact us.

      Support Refund,7X24h Service

    Support Refund,7X24h Service , Contact us.

      Call us: +86 135 995 07613

    Available on working days between 9:00 am to 6:00 pm

      Email us: sales2@industriaxplc.com

    Available 24/7 for inquiries and support

    Description

    Bently Nevada 3300/16-12-01-02-01-02-00 Dual Vibration Monitor

    Configured for dual-channel radial vibration and gap voltage processing in the Bently Nevada 3300 Machinery Monitoring System, the Bently Nevada 3300/16-12-01-02-01-02-00 (3300/16 Dual Vibration Monitor) provides direct signal conditioning and relay execution for XY proximity probe inputs.

    Suffix Breakdown & Model Matrix

    The configuration string defines fixed functional and compliance options for the module:

    Code Segment Definition Technical Meaning
    3300/16 Base module Dual-channel XY / Gap vibration monitor
    -12 Full-scale range 0 to 150 um peak-to-peak (metric scaling)
    -01 Input type 3300 / 7200 Proximitor sensor compatibility
    -02 Approval ATEX / Zone 2 compliance configuration
    -01 Relay option Epoxy-sealed alarm relays
    -02 Safety barrier Internal safety barrier integration
    -00 Trip multiply Disabled

    Hardware Specifications

    Parameter Specification
    Model 3300/16-12-01-02-01-02-00
    Brand Bently Nevada
    Origin USA
    Weight approx. 1.0 kg
    Dimensions 1-slot 3300 rack module (physical envelope not specified)
    Operating Temp 0 deg C to 65 deg C
    Power Consumption Not specified
    Channels 2 independent (Channel A / B)
    Input Type Proximitor probe (eddy-current displacement system)
    Frequency Response 4 Hz to 4000 Hz (standard) / 1 Hz low-frequency option
    Accuracy +/-0.5 percent full-scale at 25 deg C
    Outputs Buffered transducer + configurable analog recorder outputs
    Relay Output Alert and Danger dry-contact relays

    Eddy-Current Probe Scaling & Rotor Dynamics Interface

    The module processes eddy-current probe signals with fixed scaling referenced to Proximitor conversion factors (typically 100 mV/mil or 200 mV/mil depending on configuration). Gap voltage validation is performed against a controlled negative bias window (commonly referenced system behavior near -10 VDC excitation domain at the probe-proximitor interface level).

    Channel-to-channel isolation supports separation of radial vibration vectors, allowing independent X/Y rotor displacement reconstruction. Cross-talk suppression is implemented through internal analog filtering and grounded shielding architecture, minimizing phase coupling between adjacent probe channels under high shaft speed conditions.

    Rotor dynamics interpretation is derived from buffered analog outputs, enabling external systems to reconstruct orbit plots, phase reference signals, and synchronous vibration components.

    Frequently Asked Questions (FAQ)

    Q: Can the module operate with a single proximity probe input instead of two channels?
    A: Yes. Channel architecture supports single-channel operation, with the second channel left unassigned without affecting internal signal conditioning.

    Q: Does the module support hot-swap in a live 3300 rack system?
    A: Insertion and removal require system power isolation to avoid backplane transient disturbance; live hot-swap is not supported.

    Q: What happens if a channel exceeds full-scale vibration input?
    A: The signal path saturates at full-scale limit, and relay logic may trigger Danger output depending on configured setpoint thresholds.

    Field Installation Guidelines

    The module shall be installed in a valid slot of the 3300 rack system excluding slot positions 1 and 2. Backplane connector alignment must be verified prior to insertion to avoid pin damage.

    Proximitor signal cables must maintain continuous shield integrity from probe head to monitor terminal, with single-point grounding at the rack end only. Cable routing shall avoid high-energy switching conductors and VFD output lines to minimize induced noise coupling.

    Relay outputs must be wired as dry-contact circuits with external suppression provided at the load side when inductive devices are present.

    Specifications

    • Brand: Bently Nevada

    Advantages

    • High reliability in industrial environments
    • Supports continuous operation
    • Compatible with major PLC/DCS systems