Yokogawa ANB10D-415/CU2N/NDEL ESB Bus Node Unit The Yokogawa ANB10D-415/CU2N/NDEL, also cataloged as the ANB10D Node Unit for Dual-Redundant ESB Bus,...
اقرأ المزيد
رمز المنتج: ANB10D-415/CU2N/NDEL
بلد المنشأ: JAPAN
متاح في أيام العمل من الساعة 9:00 صباحًا إلى 6:00 مساءً
راسلنا عبر البريد الإلكتروني: sales2@industriaxplc.com
متاح 24/7 للاستفسارات والدعم
وصف
Yokogawa ANB10D-415/CU2N/NDEL ESB Bus Node Unit
The Yokogawa ANB10D-415/CU2N/NDEL, also cataloged as the ANB10D Node Unit for Dual-Redundant ESB Bus, operates as a dedicated hardware component for field I/O aggregation and deterministic data transfer within Yokogawa CENTUM DCS FIO networks. It executes backplane signal routing between connected I/O modules and dual-redundant Enhanced System Bus interfaces without protocol translation overhead.
Suffix Breakdown & Model Matrix
Code Element
Definition
ANB10D
Node Unit for Dual-Redundant ESB Bus
-4
Dual-redundant power supply configuration
-1
100 – 120 V AC power input
-5
Basic type, no explosion protection
/CU2N
Connector Unit for ESB Bus (no internal termination resistors)
/NDEL
Software license enabling node expansion under high-capacity FCUs
Hardware Specifications
Parameter
Specification
Model Brand
Yokogawa
Origin
Japan
Weight
10 kg
Dimensions
483 mm x 221 mm x 214 mm
Operating Temp
0 to 60 degC (derating may apply with certain comms modules)
Power Consumption
200 VA / 110 W
Power Input Range
85 to 132 V AC, 50/60 Hz ±3 Hz
I/O Capacity
8 FIO module slots
Communication Bus
Dual-redundant ESB Bus
Channel-to-Channel Isolation and Cold Junction Compensation
The ANB10D implements channel-to-channel isolation to suppress ground loop-induced noise across analog input modules. For thermocouple-configured FIO cards mounted in this node unit, cold junction compensation is executed locally at the module level, referenced to the node unit’s internal temperature sensor array. This eliminates the need for external compensation wiring while maintaining measurement accuracy across the supported input types.
Frequently Asked Questions
Q: Can the ANB10D-415/CU2N/NDEL operate with only one power supply module installed?
A: Yes. The dual-redundant power supply design permits operation with a single module, but redundancy is lost until both are installed and powered.
Q: Does the /CU2N connector unit require external termination resistors?
A: Yes. Since /CU2N lacks internal termination resistors, proper bus termination must be implemented externally at the final node position in the ESB loop.
Q: Is hot-swapping of I/O modules supported while the node unit is powered?
A: Hot-swapping is permitted only for certain FIO modules explicitly rated for live insertion. Always verify the target I/O module’s manual before removal or installation under power.
Field Installation Guidelines
Secure the node unit into a standard 19-inch rack using four M5 screws at the designated mounting points. Ensure functional grounding resistance remains below 100 ohms. Route ESB bus cables separately from high-voltage power lines to minimize electromagnetic interference. Use shielded twisted-pair cabling for all ESB connections, terminating shields at the rack ground point. Verify proper bus termination placement according to the ESB network topology before applying power.