Yokogawa ALR111-S00 Serial Communication Module Configured for serial data exchange in Yokogawa CENTUM VP distributed control systems, the Yokogawa ALR111-S00...
اقرأ المزيد
متاح في أيام العمل من الساعة 9:00 صباحًا إلى 6:00 مساءً
راسلنا عبر البريد الإلكتروني: sales2@industriaxplc.com
متاح 24/7 للاستفسارات والدعم
وصف
Yokogawa ALR111-S00 Serial Communication Module
Configured for serial data exchange in Yokogawa CENTUM VP distributed control systems, the Yokogawa ALR111-S00 (ALR111 Serial Communication Module) provides direct physical execution of RS-232C point-to-point communication links to external subsystems.
Suffix Breakdown & Model Matrix
Suffix Position
Code
Definition
Base Model
ALR111
Serial Communication Module (RS-232C, 2 ports)
Option Code 1
S
Standard type
Option Code 2
0
Basic type (No special coating/variants)
Option Code 3
0
Basic type (No explosion protection)
Hardware Specifications
Parameter
Specification
Brand
Yokogawa
Origin
Japan
Model
ALR111-S00
Weight
0.3 kg
Dimensions
Not specified in source data
Operating Temp
0 to 50 degC
Power Consumption
0.5 A at 5 VDC
Interface
RS-232C
Transmission Speed
1200, 2400, 4800, 9600, 19200, 38400 bps
Transmission Distance
Max 15 m
Connection Method
Point-to-point
Synchronization
Start-stop synchronization
Channel-to-Channel Isolation and Loop Integrity
The module interfaces support channel-to-channel isolation to prevent ground loops when interfacing with heterogeneous third-party devices such as PLCs and analyzers. Implementation of 4-20 mA HART loop protocol translation is managed via the DCS application logic. Electrical isolation is maintained through the backplane connection to the Node Unit (ANB10/ANB11/ANR10), ensuring that transient voltages on the serial lines do not propagate to the FCS processor.
Frequently Asked Questions
Q: Is the ALR111-S00 hot-swappable?
A: Yes. When installed in a dual-redundant configuration with a paired module in an adjacent slot, the unit supports online replacement without interrupting the control process.
Q: What is the maximum cable distance for RS-232C connections?
A: The maximum transmission distance is 15 meters per port. Exceeding this limit may result in signal degradation due to RS-232C voltage level attenuation.
Q: Can this module be used for multipoint networks?
A: No. The ALR111-S00 is strictly limited to point-to-point RS-232C connections. For multipoint configurations, the ALR121 (RS-422/RS-485) model must be used.
Field Installation Guidelines
Install the module into the designated slot of the Node Unit (ANB10, ANB11, ANR10, F50, AFV10, FV30, or AFV40). Use approved I/O wiring components including AKB131, AKB132, AKB133, AKB134, or 3-pair shielded cable (AKB161/AKB162). Ensure the shield drain wire is terminated at the DCS cabinet ground bus bar only, maintaining a single-point ground to mitigate EMI. Verify that the backplane power supply has sufficient current margin for the 0.5 A consumption of the module before energizing the system.
تحديد
rtl">
المزايا
موثوقية عالية في البيئات الصناعية
يدعم التشغيل المستمر، متوافق مع أنظمة PLC/DCS الرئيسية