GE IS200TBAIH1CDD Terminal Board for Analog Inputs
Configured for analog sensor signal termination and conditioning in the GE Mark VI Speedtronic turbine control system, the GE IS200TBAIH1CDD (IS200TBAI Terminal Board for Analog Inputs) provides direct physical signal routing between field devices and VAIC analog interface boards.
Hardware Specifications
Parameter
Specification
Model
IS200TBAIH1CDD
Brand
GE
Origin
United States
Weight
0.6 kg
Operating Temp
-40 deg C to +70 deg C
Power Consumption
Passive terminal interface board; power supplied through connected control system
Product Type
Terminal Board for Analog Inputs (TBAI)
System Platform
GE Mark VI Speedtronic Turbine Control System
Compatible Controller Board
VAIC (IS200VAICH1CBA and variants)
Signal Channels
20 analog input channels, 4 analog output channels
Input Signal Types
+/-5 V, +/-10 V, 0-1 mA, 4-20 mA
Output Signal Types
0-20 mA, 4-20 mA
Resolution Support
16-bit A/D and 12-bit D/A through VAIC interface
Mounting Format
DIN rail or chassis mount terminal board
Protection Features
Conformal coating and transient suppression
System Mode Support
Simplex and TMR configurations
GE Mark VI Analog Signal Interface Characteristics
The IS200TBAIH1CDD provides field wiring termination for voltage and current analog signals before transfer to the VAIC analog input/output board. The terminal interface maintains signal routing integrity between turbine sensors and the controller processing hardware.
GE Mark VI architecture uses VME-based backplane communication between control modules. The TBAI board functions as the field-side connection point, while the VAIC board performs analog conversion, scaling, and controller data processing.
Firmware and Backplane Compatibility
The board operates within the GE Mark VI control architecture through compatible VME rack interfaces. The module supports simplex and triple modular redundant configurations where multiple control paths require synchronized I/O signal availability.
The analog interface design supports I/O density scaling through Mark VI rack configurations, allowing multiple terminal boards and VAIC modules to be arranged according to turbine instrumentation requirements.
Frequently Asked Questions
Q: What analog signals can the IS200TBAIH1CDD terminate? A: The board supports voltage and current analog signals including +/-5 V, +/-10 V, 0-1 mA, and 4-20 mA inputs, with analog outputs of 0-20 mA or 4-20 mA through the VAIC interface.
Q: Does the IS200TBAIH1CDD perform analog-to-digital conversion? A: No. The terminal board provides signal termination and routing. Analog conversion functions are performed by the connected VAIC analog input/output board.
Q: Can the IS200TBAIH1CDD operate in redundant Mark VI configurations? A: The board supports installation within simplex and TMR system configurations when used with compatible Mark VI control hardware.
Field Installation Guidelines
Install the IS200TBAIH1CDD in the designated GE Mark VI control cabinet location according to the system hardware configuration. Verify terminal assignments before connecting field wiring from analog sensors.
Use shielded instrumentation cables for low-level analog signals where required. Connect cable shields according to the cabinet grounding scheme and avoid routing analog signal cables parallel to high-current power conductors.
Confirm terminal polarity and signal type before energizing the system. Inspect connectors, terminal screws, and board seating condition during installation and maintenance activities.