GE DS200TCDAH1BHE Digital to Analog Converter Board
Configured for digital signal conversion in the GE Mark V turbine control system, the GE DS200TCDAH1BHE (DS200TCDA Digital to Analog Converter Board) provides direct electrical conversion from processor-generated digital data to analog output signals for turbine control interfaces.
Hardware Specifications
Parameter
Specification
Model
DS200TCDAH1BHE
Brand
GE General Electric
Origin
United States
Weight
0.8 kg
Dimensions
233 mm x 160 mm x 25 mm
Operating Temp
-30 to +65 deg C
Power Consumption
Supplied through +5 VDC and +/-15 VDC backplane power
Product Type
Digital I/O Boards
Series
Mark V
Functional Acronym
TCDA
Input Voltage
+5 VDC, +/-15 VDC from backplane
Digital Input Interface
16-bit parallel bus from CPCA/SDCC boards
Analog Output Range
+/-10 VDC, 4-20 mA
DAC Resolution
12-bit
Isolation Rating
2500 Vrms
Response Time
< 5 ms signal conversion
Diagnostics
Front-panel LEDs: Run, Fail, Output Status
Redundancy Support
Dual/triple modular redundancy compatible
Mounting Type
Rack mount, single-slot
Deterministic Network and I/O Density Characteristics
The DS200TCDAH1BHE operates as an analog interface expansion board within the GE Mark V control architecture. The module receives digital control values through the processor board interface and performs digital-to-analog conversion for connected field devices. I/O density scaling is achieved through dedicated conversion channels supporting multiple analog output requirements within the rack system.
The board interfaces with CPCA and SDCC processor modules through the Mark V backplane structure. Firmware flash compatibility and processor configuration must match the installed control system revision to maintain correct signal mapping and output execution.
Frequently Asked Questions
Q: What type of signals does the DS200TCDAH1BHE convert? A: The board converts 16-bit digital control data from processor boards into analog output signals including +/-10 VDC and 4-20 mA.
Q: Does the DS200TCDAH1BHE contain independent control processing? A: No. The board performs digital-to-analog conversion functions and relies on connected Mark V processor boards for control logic execution.
Q: Which processor boards interface with the TCDA board? A: The module interfaces with CPCA and SDCC processor boards within the GE Mark V control system.
Field Installation Guidelines
Install the DS200TCDAH1BHE in the designated Mark V rack slot and verify proper backplane connector alignment before energizing the system. Confirm that analog output wiring matches the approved terminal configuration and signal requirements.
Route analog signal cables separately from high-power conductors to reduce electrical noise coupling. Cable shielding should be grounded according to the site grounding standard. Verify polarity, terminal tightness, and processor board compatibility before commissioning.