أكثر من 100,000 قطعة من PLC وDCS وDrive وTSI وMRO متوفرة في المخزون. تعرف على المزيد

Bently Nevada 3701/55 323073-01 Relay Output Module

Bently Nevada 3701/55 323073-01 Relay Output Module

شكل المنتج

Bently Nevada 3701/55 323073-01 Relay Output Module The Bently Nevada 3701/55 323073-01, also cataloged as the 3701/55 Relay Output Module,... اقرأ المزيد

رمز المنتج: 3701/55 323073-01
بلد المنشأ: USA

      100% أصلي وحقيقي

    هل تحتاج إلى مخزون كبير؟ تواصل معنا .

      100% جديد تمامًا وجاهز للشحن

    هل تحتاج إلى مخزون كبير؟ تواصل معنا .

      دعم استرداد الأموال، خدمة 7X24 ساعة

    دعم استرداد الأموال، خدمة 7X24 ساعة، اتصل بنا .

      اتصل بنا: +86 135 995 07613

    متاح في أيام العمل من الساعة 9:00 صباحًا إلى 6:00 مساءً

      راسلنا عبر البريد الإلكتروني: sales2@industriaxplc.com

    متاح 24/7 للاستفسارات والدعم

    وصف

    Bently Nevada 3701/55 323073-01 Relay Output Module

    The Bently Nevada 3701/55 323073-01, also cataloged as the 3701/55 Relay Output Module, operates as a dedicated hardware component for relay contact execution within the Bently Nevada ADAPT ESD system.

    Hardware Specifications

    Parameter Specification
    Model 3701/55 323073-01
    Brand Bently Nevada
    Product Type Relay Output Module
    System Platform ADAPT ESD System
    Module Function Relay contact output execution for shutdown and annunciation circuits
    Relay Contacts 5 relay contacts per module
    Relay Configuration 2 independent CPU-driven relays, 2 configurable relays, 1 system relay
    Voting Architecture Supports 2oo3 relay voting configuration
    Logic Execution Time 2 ms nominal
    Relay Toggle Time 8 ms
    System Response Time Less than 10 ms
    Operating Voltage 18 to 36 VDC
    Power Consumption 24 W typical, 35 W maximum
    Operating Temp -30 deg C to +65 deg C
    Storage Temp -45 deg C to +85 deg C
    Relative Humidity 0% to 95%, non-condensing
    Vibration Resistance IEC 60068-1 compliant, 3 g at 3-57 Hz, 5 g at 57-500 Hz
    Weight Approx. 1.5 kg
    Dimensions Not specified
    Housing Material Cast aluminum module housing with industrial protective coating
    Certifications SIL 3 (IEC 61508), API 670, API 612, ATEX, IECEx, cULus, CE

    Eddy-Current Signal Processing and Machinery Protection Interface

    The Bently Nevada 3701/55 platform is designed for machinery protection applications where relay outputs are driven by processed vibration, speed, and shutdown logic signals. The ADAPT ESD architecture supports integration with rotating equipment monitoring functions, including overspeed detection and emergency shutdown execution.

    The system design supports verification of proximity probe input conditions, including eddy-current probe scaling and gap voltage validation. The typical proximity measurement reference uses -10 VDC gap voltage targets for probe operating range verification. Signal processing functions are configured to maintain rotor dynamics monitoring accuracy and reduce measurement errors caused by cross-talk between adjacent sensing channels.

    Frequently Asked Questions

    Q: Does the 323073-01 Relay Output Module support redundant relay operation?
    A: Yes. The module supports configurable relay arrangements, including 2oo3 voting logic when integrated within the TMR architecture of the ADAPT ESD system.

    Q: What is the maximum electrical response time of the relay output function?
    A: The nominal logic execution time is 2 ms, the relay toggle time is 8 ms, and the combined system response time is less than 10 ms.

    Q: Can the relay output module operate independently without the ADAPT ESD system controller?
    A: No. The 323073-01 is designed as a system component and requires integration with the ADAPT ESD platform for logic processing and relay control.

    Field Installation Guidelines

    • Install the relay output module inside an enclosure that meets the required environmental protection level for the application.
    • Verify correct module orientation and mechanical mounting before applying system power.
    • Route relay output wiring separately from high-voltage power cables and high-frequency switching conductors to minimize electrical interference.
    • Use appropriate shield grounding practices for connected machinery protection signal circuits.
    • Confirm relay contact assignments and safety logic configuration before commissioning.
    • Verify proximity monitoring channels, shutdown logic, and relay actuation paths during functional testing.
    • Follow the applicable API 670 machinery protection installation requirements when integrating with rotating equipment systems.

    تحديد

    • rtl">

    المزايا

    • موثوقية عالية في البيئات الصناعية

    • يدعم التشغيل المستمر، متوافق مع أنظمة PLC/DCS الرئيسية

    Customer Reviews

    Be the first to write a review
    0%
    (0)
    0%
    (0)
    0%
    (0)
    0%
    (0)
    0%
    (0)
    أرسل لنا رسالة!

    هل تحتاج إلى مخزون كبير؟ تواصل معنا.

    مجموعات قد تعجبك أيضًا

    المنتجات التي تمت مشاهدتها مؤخرًا

      Login

      نسيت كلمة السر؟

      ليس لديك حساب حتى الآن؟
      Create account