Yokogawa ANB10D-425/CU2T/NDEL ESB Bus Node Unit Configured for deterministic I/O aggregation in the CENTUM VP and CENTUM CS 3000 distributed...
اقرأ المزيد
رمز المنتج: ANB10D-425/CU2T/NDEL
بلد المنشأ: JAPAN
متاح في أيام العمل من الساعة 9:00 صباحًا إلى 6:00 مساءً
راسلنا عبر البريد الإلكتروني: sales2@industriaxplc.com
متاح 24/7 للاستفسارات والدعم
وصف
Yokogawa ANB10D-425/CU2T/NDEL ESB Bus Node Unit
Configured for deterministic I/O aggregation in the CENTUM VP and CENTUM CS 3000 distributed control systems, the Yokogawa ANB10D-425/CU2T/NDEL (ANB10D ESB Bus Node Unit) provides direct physical and electrical execution of field signal routing through dual-redundant ESB bus interfaces.
Suffix Breakdown & Model Matrix
Code Segment
Description
ANB10D
Dual-redundant ESB Bus Node Unit
-4
Dual-redundant power supply modules
2
220–240 V AC power input (50/60 Hz)
5
Basic type, no explosion protection
/CU2T
Connector unit with integrated bus terminator
/NDEL
Supplied without digital labeling
Hardware Specifications
Parameter
Specification
Model Brand
Yokogawa ANB10D-425/CU2T/NDEL
Origin
Japan
Weight
10.0 kg (empty)
Dimensions
19-inch rack mount
Operating Temp
0 to 50 degC
Storage Temp
-20 to 70 degC
Power Supply Voltage
220–240 V AC
Frequency
50/60 Hz
Withstanding Voltage
1500 V AC between power and ground terminals
Insulation Resistance
≥ 20 MΩ @ 500 V DC
I/O Slots
8 FIO module slots
Communication Interface
Dual-redundant ESB Bus
FOUNDATION Fieldbus & Profibus PA Connectivity
The ANB10D supports integration with FOUNDATION Fieldbus H1 and Profibus PA segments when paired with compatible FIO communication modules. Bus arbitration occurs at the node level without impacting the deterministic ESB cycle time. Channel-to-channel isolation preserves signal integrity across mixed analog and discrete loads, ensuring compliance with intrinsic safety loop constraints in classified areas.
Frequently Asked Questions
Q: Can the unit operate with only one power supply module installed?
A: Yes, but redundancy is lost; both modules should be installed for fault-tolerant operation.
Q: Does the /CU2T connector require additional termination?
A: No. The integrated terminator is preconfigured for the final position in the ESB bus chain.
Q: What is the function of the /NDEL option in field wiring?
A: /NDEL indicates omission of pre-printed digital label strips; wire identification must be applied manually according to site documentation.
Field Installation Guidelines
Secure the unit in a 19-inch rack using specified mounting hardware. Route ESB bus cables away from high-voltage power lines to minimize electromagnetic interference. Use shielded twisted-pair cable for all bus connections, bonding shields to the functional ground terminal at the rack only. Verify that each power feed originates from an independent source, preferably via separate uninterruptible power supplies. Confirm that installed I/O module total current draw does not exceed the power supply rating before energizing the node.
تحديد
rtl">
المزايا
موثوقية عالية في البيئات الصناعية
يدعم التشغيل المستمر، متوافق مع أنظمة PLC/DCS الرئيسية