Honeywell 8C-PDILA1 51454471-175 Series 8 Digital Input Module Configured for 24 VDC discrete signal acquisition in the Honeywell Series 8...
اقرأ المزيد
رمز المنتج: 8C-PDILA1 51454471-175
بلد المنشأ: USA
متاح في أيام العمل من الساعة 9:00 صباحًا إلى 6:00 مساءً
راسلنا عبر البريد الإلكتروني: sales2@industriaxplc.com
متاح 24/7 للاستفسارات والدعم
وصف
Honeywell 8C-PDILA1 51454471-175 Series 8 Digital Input Module
Configured for 24 VDC discrete signal acquisition in the Honeywell Series 8 I/O system, the Honeywell 8C-PDILA1 51454471-175 (8C-PDILA1 Digital Input Module) provides direct electrical monitoring of field input states through 32 isolated channels.
Hardware Specifications
Parameter
Specification
Model
8C-PDILA1 51454471-175
Brand
Honeywell
Product Type
S8 DI 24V IOM (32), Coated
Series
Honeywell Series 8 I/O
Origin
USA
Weight
0.3 kg
Dimensions
6 x 15.2 x 14.3 cm
Power Consumption
95 mA module current rating
Input Channels
32 Digital Input Channels
Input Voltage Rating
24 VDC
DI Power Voltage Range
18 to 30 VDC
ON Sense Voltage/Current
13 VDC minimum or 3 mA minimum
OFF Sense Voltage/Current
5 VDC maximum or 1.2 mA maximum
Input Impedance
4.2 KOhm
Galvanic Isolation
1000 VAC RMS or +/-1500 VDC system isolation
Isolation Technique
Optical isolation in IOM
Absolute Delay Across Input Filter and Isolation
5 ms +/- 20%
Field Resistance for Guaranteed ON Condition
300 Ohm maximum at 15 VDC
Field Resistance for Guaranteed OFF Condition
30 KOhm minimum at 30 VDC
Coating Type
Conformal coated electronics protection
DCS Signal Isolation and Process I/O Characteristics
The Honeywell 8C-PDILA1 51454471-175 integrates digital signal acquisition with optical isolation for Series 8 I/O architectures. The module monitors 24 VDC field signals and transfers discrete states through the IOTA interface.
Furthermore, the module supports channel-level electrical separation between field wiring and system electronics. The galvanic isolation design reduces interference transfer from external field circuits and supports industrial control cabinet installations.
The Honeywell Series 8 I/O platform uses integrated IOM and IOTA construction. Therefore, the module receives system power and field connections through the Input Output Termination Assembly without requiring a separate chassis.
The module also supports optional redundancy. A redundant IOM can be installed on the same IOTA to provide system-level availability without external redundancy cabling or additional control devices.
Frequently Asked Questions
Q: What type of input signals does the Honeywell 8C-PDILA1 51454471-175 accept? A: The module accepts 24 VDC discrete input signals through 32 digital input channels. The supported DI power voltage range is 18 to 30 VDC.
Q: Does the 8C-PDILA1 provide electrical isolation between field signals and system circuits? A: Yes. The module uses optical isolation inside the IOM and provides galvanic isolation rated at 1000 VAC RMS or +/-1500 VDC for system isolation.
Q: How is redundancy configured for this digital input module? A: The module supports optional redundancy by installing a second IOM on the same IOTA. The configuration does not require external redundancy cables or additional redundancy control hardware.
Field Installation Guidelines
Install the 8C-PDILA1 51454471-175 directly into the compatible Honeywell Series 8 IOTA position.
Verify that field wiring matches the 24 VDC digital input requirements before energizing the module.
Separate digital input wiring from high-current power cables to reduce electrical interference.
Connect cable shields according to the control cabinet grounding practice defined for the installation site.
Confirm correct terminal assignments at the IOTA before applying field power.
Inspect module seating and connector engagement during installation to maintain proper backplane and termination connections.