Yokogawa NFCP502-S05 Style S2 CPU Module
The Yokogawa NFCP502-S05 Style S2, also cataloged as the NFCP502 CPU Module, operates as a dedicated hardware component for regulatory and sequence control execution within the STARDOM FCN-500 Autonomous Controller system. It provides direct Ethernet-based network communication and deterministic task execution for control logic applications.
Hardware Specifications
Parameter
Specification
ModelBrand
Yokogawa NFCP502-S05 Style S2
Origin
Japan
Weight
1.5 kg
Dimensions
Standard FCN-500 module footprint
OperatingTemp
0 degC to 55 degC
PowerConsumption
Typical 10 W (dependent on I/O load)
Processor
Atom E3815 1.46 GHz
MainMemory
256 MB ECC
StaticRAM
2 MB ECC, battery-backed
SecondaryMemory
1 GB on-board flash
ExternalMedia
SDHC 4 to 32 GB, Class 10
SerialPort
1 RS-232-C port (D-sub 9 pins, male)
CommunicationMethod
Full/Half duplex, asynchronous
BaudRate
0.3 to 115.2 kbps selectable
EthernetPorts
4 × RJ-45, 10/100/1000 Mbps
I/OInterface
SB bus (duplex)
ControlTasks
Max 16 concurrent, 16 priority levels
Humidity
5% to 95% RH, non-condensing
VibrationResistance
0.15 mm P-P (5–58 Hz), 1 G (58–150 Hz)
ShockResistance
15 G, 11 ms (power off, X/Y/Z)
CorrosiveGasResistance
ANSI/ISA S71.04 Class G2
Altitude
≤ 2000 m
Process Control Technical Features
The NFCP502-S05 Style S2 supports channel-to-channel isolation across Ethernet ports and I/O buses to prevent cross-interference. Each analog loop can interface with 4-20 mA HART signals, and FOUNDATION Fieldbus/Profibus PA connectivity is fully supported for distributed control system integration. Cold junction compensation (CJc) is applied to ensure temperature measurement consistency across all input channels.
Frequently Asked Questions
Q: What is the maximum hot-swap delay for dual-redundant CPUs? A: Failover between redundant CPUs is ≤100 ms under normal operating conditions.
Q: Can the module operate with all Ethernet ports active simultaneously? A: Yes. Ports 1 and 2 support redundant control networks; Ports 3 and 4 handle peripheral traffic independently.
Q: Are SD cards hot-swappable? A: SDHC cards can be inserted or removed while the module is powered down; active insertion during runtime is not supported.
Field Installation Guidelines
Mount the CPU module in the FCN-500 rack with proper alignment to the backplane connectors.
Ensure all Ethernet ports are properly shielded and grounded. Use twisted pair cabling with shield termination at one end to minimize EMI.
Maintain minimum spacing from heat-generating modules to preserve natural convection airflow.
Avoid routing high-current or high-voltage conductors near control signal cables.
Verify the orientation of the RS-232-C connector and secure locking screws to prevent mechanical stress.