Keterangan
Yokogawa EC402-51 ESB Bus Coupler Module
The Yokogawa EC402-51, also cataloged as the EC402 ESB Bus Coupler Module, operates as a dedicated hardware component for high-speed ESB bus master interfacing within CENTUM VP and CS 3000 distributed control systems.
Suffix Breakdown & Model Matrix
EC402: ESB Bus Coupler Module for N-IO / FIO, 2-Port type
-5: Standard type with no explosion protection
1: ISA Standard G3 conformal coating for corrosion and chemical resistance
Hardware Specifications
Parameter
Specification
ModelBrand
Yokogawa EC402-51
Origin
Japan
Weight
Approx. 0.24 kg
Dimensions
32.8 mm × 130.0 mm × 129.5 mm
OperatingTemp
-10 degC to +60 degC
PowerConsumption
0.5 A
Function
ESB Bus Master Interface
Compatible Systems
CENTUM VP / CS 3000 (AFV30, AFV40, A2FV50, A2FV70 FCUs)
TransmissionSpeed
128 Mbps
ConnectableUnits
Upper: Max. 9, Lower: Max. 9, Total Max: 13
TransmissionDistance
Upper: Max. 10 m, Lower: Max. 10 m, Total Max: 20 m
DataBufferSize
128 KB
DCS Bus Communication and Channel Isolation
The EC402-51 implements deterministic ESB bus communication with isolated upper and lower ports, minimizing cross-channel interference. Dual-redundant deployment is supported by pairing two modules in adjacent FCU slots to maintain continuous I/O data flow during maintenance or module failure. The module’s data buffering ensures low-latency response times (~10 ms) for remote ESB node interactions.
Frequently Asked Questions
Q: Can the EC402-51 be hot-swapped while the FCU is online? A: No. Replacement requires controlled FCU shutdown or redundant module support to avoid data loss.
Q: What is the maximum number of ESB nodes supported per EC402-51 module? A: Up to 9 nodes on the upper port and 9 nodes on the lower port, with a system total of 13 nodes.
Q: How is the module protected against harsh environmental conditions? A: The EC402-51 with suffix “-1” includes ISA Standard G3 conformal coating, providing resistance to corrosive chemical environments.
Field Installation Guidelines
Mount module directly into designated FCU slot with proper slot alignment
Maintain grounding continuity to FCU backplane and chassis earth
Use standard Yokogawa YCB301 ESB bus cables, observing maximum distances of 10 m per port
Keep bus cabling physically separated from high-voltage lines to prevent EMI
Verify dual-redundant modules are installed in correct slot pairs for continuous bus availability
Ensure airflow clearance around adjacent modules to prevent thermal accumulation