Yokogawa ARM55C-000 Mechanical Relay Output Board
Configured for dry-contact relay output switching in CENTUM VP and CENTUM CS 3000 FIO subsystems, the Yokogawa ARM55C-000 (ARM55C Mechanical Relay Output Board) provides direct physical and electrical execution of field load control through isolated mechanical relay contacts.
Suffix Breakdown & Model Matrix
Code
Description
ARM55C
Mechanical Relay Output Board, 32-point dry contact type
-0
Basic specification
0
19-inch rack-mountable configuration
0
Basic type
Hardware Specifications
Parameter
Specification
ModelBrand
Yokogawa ARM55C-000
Origin
Japan
Weight
Approx. 2.2 kg
Dimensions
482.6 mm (W) x 132.5 mm (H) x 298.5 mm (D)
OperatingTemp
0 to 50 degC
PowerConsumption
Max. 0.85 A at 24 VDC (approx. 26 W)
Product Type
Mechanical Relay Output Board
Number of Channels
32 points
Rated Supply Voltage
24 VDC
Control Logic Signal
5 VDC, 10 mA
Maximum AC Load
250 VAC, 2 A per channel
Maximum DC Load
30 VDC, 2 A or 125 VDC, 0.1 A per channel
Minimum Load
5 VDC, 10 mA
Insulation Resistance
10 MOhm minimum at 500 VDC
Dielectric Strength
2 kVAC field-to-case
Humidity
10 % to 90 % RH, non-condensing
Mounting Method
19-inch rack, 3U height
Channel Isolation and DCS Output Interface
The ARM55C-000 functions as an isolation interface between digital output modules and field-side loads. Mechanical relays provide galvanic separation between control circuitry and output circuits, reducing direct electrical coupling between channels. The board is designed for integration with Yokogawa FIO architectures and can be deployed in single or dual-redundant output arrangements using compatible digital output modules and signal cables.
Frequently Asked Questions
Q: Does the ARM55C-000 support hot-swapping during operation? A: No. Removal or installation should be performed with the associated I/O circuit de-energized to avoid unintended relay state transitions and wiring faults.
Q: Can the board be used in redundant output configurations? A: Yes. The ARM55C-000 supports dual-redundant configurations when installed with the required redundant output modules and associated signal cable assemblies.
Q: Does the board require firmware updates? A: No. The ARM55C-000 is a hardware relay board and contains no field-upgradable firmware. Firmware management applies to the connected control modules rather than the relay board itself.
Field Installation Guidelines
Install the board in a compatible 19-inch rack using the designated mounting hardware.
Verify that field wiring is terminated to the correct M3.5 terminals and power wiring to the designated M4 terminals.
Route output wiring separately from high-voltage power cables to minimize electromagnetic coupling.
Connect cable shields according to site grounding standards and DCS cabinet grounding practices.
Confirm contact ratings of connected loads before energization to prevent relay contact overstress.
Inspect terminal screw tightness during commissioning and scheduled maintenance intervals.
Perform insulation and continuity checks prior to connecting field loads.